Emerson Switch 3ADTS User Manual

Page of 8
Installation Manual 
 
ASCO 3ATS, 3ADTS, 3NTS, 3NDTS 
381333-406 
ASCO Power Technologies 
Page 1 
 
 
 
 
 
 
 
DANGER is used in this manual to warn of a 
hazard situation which, if not avoided, will result in 
death or serious injury. 
 
 
 
 
 
WARNING is used in this manual to warn of a 
hazardous situation which, if not avoided, could 
result death or serious injury. 
 
 
 
CAUTION is used in this manual to warn of a 
hazardous situation which, if not avoided, could 
result in minor or moderate injury. 
 
Rating Label 
Each transfer switch contains a rating label to define the loads 
and fault circuit withstand/closing ratings.  Refer to the label 
on the transfer switch for specific values. 
 
 
 
 
 
Do not exceed the values on the rating label. 
Exceeding the rating can cause person injury or 
serious equipment damage. 
 
An experienced licensed electrician must install the transfer 
switch. 
Installation 
These transfer switches are factory wired and tested.  
Installation requires mounting, connecting service cables, and 
connecting engine start and auxiliary control circuits (if 
required.). 
 
 
 
 
 
 
 
 
Supporting Foundation 
The supporting foundation for the enclosure must be level and 
straight.  Refer to the applicable enclosure outline drawing 
included with the transfer switch for all mounting details 
including door opening space. 
If bottom cable entry is used, the foundation must be prepared 
so that the conduit stubs are located correctly.  Refer to the 
enclosure outline drawing for specified area and location.  
Provide cable bending space and 1 inch minimum clearance to 
live metal parts.  When a concrete floor is poured, use 
interlocking conduit spacer caps or a wood or metal template 
to maintain proper conduit alignment. 
 
Mounting 
Refer to the outline and mounting diagram and mount the 
transfer switch according to details and instructions shown on 
the diagram.  Mount it vertically to a rigid supporting 
structure.  Level all mounting points by using flat washers 
behind the holes to avoid distortion of the transfer switch. 
 
 
 
 
Protect the transfer switch from construction grit 
and metal chips to prevent malfunction or 
shortened life of the transfer switch. 
 
381333-406 
Refer to the outline and wiring drawings provided 
with the 3ATS, 3NTS, 3ADTS, or 3NDTS for all 
installation and connection details and accessories.
    DANGER 
 
 
 
 
!
      WARNING 
 
 
 
 
!
      CAUTION 
 
 
 
 
!
Refer to User’s Guide 381333-400 for the Goup G 
Controller status display messages, time delays, 
pickup and dropout settings, and adjustments. 
 
 3ATS, 3ADTS, 3NTS, 3NDTS 
G-design 1600-3000 A Transfer Switches 
Installation Manual 
      WARNING 
 
 
 
 
!
NOTICE
INSTALLATION 
Mounting ..........................................................1
Power Connections .........................................2
Engine Starting Contacts.................................2
 
FUNCTIONAL TEST 
1- Manual Operation........................................3
2- Voltage Checks ...........................................4
3- Electrical Operation .....................................6
 
TESTING & SERVICE 
Transfer Test ...................................................6
Preventive Maintenance ..................................6
Manual Load Transfer .....................................6
 
TROUBLESHOOTING ....................................7
 
INDEX..............................................................8
Table of Contents