Installation/Configuration Notes
Compatibility Information
The FMM‑462 Series Addressable Manual Stations are
compatible with the following products:
Category
Product ID
Product Description
Control
D7212G
Control panel
Panels:
D7412G
Control panel
 
D9412G
Control panel
 
D9124
Addressable FACP
Modules
D9127U
POPIT module
Mounting Considerations
The FMM‑462 manual stations are for indoor use only.
The FMM‑462 or FMM‑462‑D and the wiring from the
control panel data expansion loop fit into a single-gang
back box for flush mounting. Use the larger
FMM‑100BB‑R Back Box for surface mounting and to
provide additional room for system wiring and the
module.
Parts Included
Quant.
Component
1
Manual station
1
D9127U POPIT module
1
FMM‑100GR scored acrylic breakrod
1
D102 Key (1358)
1
Literature pack
Technical Specifications
Environmental Considerations
Temperature (operating):
+14°F to +120°F (-10°C to +49°C)
Mechanical Properties
Activation Force:
5 lb (2.3 kg)
Alarm Response Time:
1 sec (approximately)
Dimensions (HxWxD):
4.75 in. x 3.2 in. x 0.875 in.
(12.1 cm x 8.1 cm x 2.2 cm)
Material:
Painted die‑cast metal, plated steel back
and painted steel front
Power Requirements
Current (alarm):
0.8 mA
Current (normal):
0.5 mA
Voltage (operating):
7 VDC to 15 VDC supplied by the control
panel
Ordering Information
FMM‑462 Single‑Action Manual Station
A UL-listed initiating device compatible with the Bosch
Security Systems, Inc. G Series Control Panels and the
D9124 Fire Alarm Control Panel (FACP)
Order number 
FMM-462
FMM‑462‑D Double‑Action Manual Station
A UL-listed initiating device compatible with the Bosch
Security Systems, Inc. G Series Control Panels and the
D9124 Fire Alarm Control Panel (FACP)
Order number 
FMM-462-D
Accessories
D102 Replacement Key
Replacement key (#1358) for the D101 lock.
Order number 
D102
FMM‑100BB‑R Surface‑mount Back Box (red)
Red cast‑metal back box
Order number 
FMM-100BB-R
FMM‑100GR Scored Acrylic Break Rods
Scored acrylic rods (12 per package)
Order number 
FMM-100GR
 
2 | FMM‑462 Series POPIT Addressable Manual Stations