DKS Enterprises PC Compatible Multi-Door Access Controller 1838 User Manual

Page of 49
 
3.6  FOUR-DIGIT ENTRY CODE 
A DoorKing slave keypad (P/N 1814-075) is required if four-digit entry codes are going to be used to 
access a door or gate.  It is important to understand that four-digit entry codes are not the same as a 
five-digit PIN (Personal Identification Number) code inputted to the system from a weigand keypad.  
Four-digit entry codes can only activate relay 1 or relay 2 on the 1842-010 circuit board, regardless if 
Tracker expansion boards are used or not.  If Tracker expansion boards are controlled by relay 2, the 
four-digit entry codes must be set to activate relay 1.  If both relays are used to control Tracker 
expansion boards, then four-digit entry codes cannot be used and should not be programmed into the 
system.  Under this condition, if digital PIN codes are desired, use a weigand keypad (P/N 1815-050 
or 1815-051) connected to a Tracker board. 
 
3.6.1 
Programming Four-digit Entry Codes 
1. Press 
* 0 2 and enter the four-digit MASTER CODE _ _ _ _ (beep). 
2. 
Enter the directory code (1, 2, 3 or 4 digits depending on what was programmed in 
3.4.1) then press * (beep). 
3. 
Enter the four-digit entry code _ _ _ _ then press * (beep). 
4. 
Repeat steps 2 and 3 to enter additional entry codes. 
5. Press 
0 # TOGETHER to end this programming step (beeeeeep). 
 
 
3.6.2 
Delete Four-digit Entry Codes 
1. Press 
* 0 2 and enter the four-digit MASTER CODE _ _ _ _ (beep). 
2. 
Enter the directory code (1, 2, 3 or 4 digits depending on what was programmed in 
3.4.1) then press * (beep). 
3. Press 
# # # # * (beep). 
4. 
Repeat steps 2 and 3 to delete more entry codes. 
5. Press 
0 # TOGETHER to end this programming step (beeeeeep). 
 
 
3.6.3 Entry 
Code 
Ranges 
Four-digit entry codes can be made to activate relay 1 or relay 2 or any combination of relays by 
programming HI and LOW ranges for each relay.  Ranges may overlap, which will cause more than 
one relay to activate if this is desired.  For example, if the low boundary for relay 1 and 2 is 2000, and 
the hi boundary is 3000 for relay 1 and 4000 for relay 2, then entry codes between 2000 and 3000 will 
activate both relays, and entry codes between 3001 and 4000 will only activate relay 2. 
 
1. Press 
* 1 2 and enter the four-digit MASTER CODE _ _ _ _ (beep). 
2. Press 
1 * to set relay 1, or 2 * to set relay 2 boundaries. 
3. 
Enter the four-digit low boundary _ _ _ _ then press * (beep).   
4. 
Enter the four-digit high boundary _ _ _ _ then press * (beep).   
5. 
Repeat steps 2, 3, and 4 to set the other relay boundaries (or proceed to step 7). 
6. Press 
0 # TOGETHER to end this programming step (beeeeeep). 
 
Page 
34  