Honeywell 805595 User Manual

Page of 46
IQ8Wireless transponder for wall mounting 
 
FB 798941 / 10.06
 
31 
 
LED 1 
Operation (green) 
Lits in normal operation 
LED 2 
Common fire alarm (red) 
Lits when the fire alarm of an assigned wireless device has been detected. 
The relay >common fire alarm< is activated. 
LED 3 
Common trouble (yellow), display not latched 
Lits when a fault message from the IQ8Wireless transponder or an assigned 
wireless device has been detected. Activation of the >common fault< relay is 
interrupted and the relay contact changes position. 
LED 4 
Initialisation (yellow) 
Lits during the switch-on/learning process of the IQ8Wireless transponder while the 
wireless devices are being recognised.  
Housing screw to open/close the transponder housing 
 
LED-indicators on the board  
A
 
Status indication of the Analog loop communication 
Both LED (red and green) twinkle while the data communication on the connected 
loop of the FACP IQ8Control is active. 
 
 red 
 green 
LED-incicator for the wireless operation mode 
B
 
Off 
 
flashes  
(2Hz) 
 
Normal operation mode 
All assigned wireless devices operates as required in 
the frequenzy-hopping mode. 
 
ON 
 
flashes  
(2Hz) 
Normal operation with a communication fault 
At least one wireless device is out of the frequenzy-
hopping mode and is automatically searched in the 
base channel. This fault is indicated at the FACP 
after approx. 40-60s. If the wireless device could be 
automatically found within this time the red LED goes 
out.  
 
Flashes alternately  
(2Hz) 
Installation mode (restricted operation) 
e.g. during field strength measurement, transponder 
or detector data assignment or while searching a 
wireless device. 
 
Flashes common 
(2Hz) 
Malfunction – Wireless mode disabled 
Wireless communication not possible 
Πtransponder 
is defect (return to factory) 
 
Flashes common 
each 7 seconds 
Disablement – wireless mode off 
The wireless operation mode is automatically 
disabled due to no wireless is assigned or present.