VII. Trouble Shooting
PROBLEM
CAUSE
SOLUTION
No hot water at faucet
Boiler does not operate
Refer to boiler installation instructions
Check main service  switch
Check fused disconnect
Circulator does not operate
Check power supply
Check shaft coupling
Improper aquastat setting or calibration
Turn tank aquastat to higher setting
Zone valve does not open (if used)
Check power supply
Electrical problem (relay, wiring, fuse, etc.)
Check fuse and replace
Check circuit breaker and reset (if  applicable)
Check power supply
Scale build-up
If boiler, circulator and tank are operating satisfactorily, coil
may have scale coating. See Section VI: Service Instructions
Clogged cold  water filter or boiler  supply
strainer (if used)
Clean or replace filter or strainer
Insufficient hot water
Aquastat setting too low
Adjust aquastat to higher setting
Undersized  boiler with no priority to
domestic hot water
Rewire for priority
Peak use of hot water is greater than tank
storage capacity
Determine peak usage and compare to tank volume
Scale build-up
If boiler, circulator and tank are operating satisfactorily, coil
may have scale coating. See Section VI: Service Instructions
Faulty tank aquastat
Replace aquastat
Water at faucet too hot
Aquastat set too high
Lower aquastat setting
Improper system plumbing
Compare plumbing to Section III: Piping
Improper system wiring
Compare wiring to Section IV: Electrical
Boiler cycles more
than 5 times per
day in summer
Excessive demand
Reduce demand or consider larger tank
Faulty aquastat
Replace aquastat
Boiler high limit set too low
Increase boiler high limit setting
Scale Build-up
If boiler, circulator and tank are operating satisfactorily, coil
may have scale coating. See Section VI: Service Instructions