6.  AC ELECTRICAL SUPPLY 
 
The charger must be connected to either a single phase or three phase, 60 Hertz 
(
± 2%) AC power source.  Three phase chargers cannot be powered with a single 
phase source. 
 
The following transformer options are available: 
 
TABLE 1 – INPUT VOLTAGE CHOICES 
 
Single phase  
Three phase 
208/240/480VAC, 60Hz 
208/240/480VAC, 60Hz 
 
Only the AC input wire configuration for multi-input chargers can be changed. Follow 
Figure 1 (page 6) for single-phase input or Figure 2 (page 7) for three-phase input 
transformers. A qualified electrical contractor should perform this adjustment. 
 
6.1. BRANCH CIRCUIT PROTECTION  
 
The charger comes with an internal supplementary protective device rated to 
accommodate the highest possible current and voltage for that model. 
 
 
CAUTION:   TO REDUCE THE RISK OF FIRE, USE ONLY ON CIRCUITS PROVIDED 
WITH BRANCH CIRCUIT PROTECTION CONSISTENT WITH THE 
CURRENT INDICATED ON THE FRONT PANEL-RATING LABEL AND 
IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE, 
ANSI/NFPA 70.