ENERGY MANAGEMENT RECOVERY 
(EMR)
When  the  EMR  feature  is  activated  the  thermostat’s
microcomputer  calculates  the  time  it  will  take  to  change  the 
room  temperature  to  the  next  heat  or  cool  program  setting. 
Then  the  thermostat  will  start  the  system  before  the  next 
programmed period so that the desired temperature is reached 
at or near the beginning of the period (the thermostat calculates
15  minutes  for  every  1°F  temperature  change). This  feature
provides  better  efficiency  by  allowing  gradual  temperature 
changes.
For  example:  The  thermostat  is  programmed  to  provide  an 
overnight  heating  temperature  of  66°F,  and  during  the  next
program  period,  beginning  at  6:00  AM,  the  programmed
temperature is 70°F. With EMR activated, the thermostat will
automatically start the heating system at 5:00 AM, so that the
programmed  temperature  of  70°F  is  reached  by  about  6:00
AM.
If  the  overnight  room  temperature  drops  only  to  68°F,  the
thermostat will start the system at 5:30 to reach the programmed
temperature of 70°F at 6:00.
The thermostat is shipped with the EMR feature 
active, which 
means that the thermostat will start the heating system before 
the beginning of the next program period.
To deactivate the EMR function, see the Configuration menu 
on Page 5). The thermostat will then wait until the programmed
time to start the system for a temperature change.
INSTALLATION 
WIRING DIAGRAMS 
R
C
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G
W
Figure 2. Typical wiring diagram for single transformer single stage systems
TRANSFORMER
(Class II Current Limited)
Changeover
Relay*
Y
O/B
Compressor
Contactor
* Changeover Relay is energized in COOL when O/B switch is in the “O” position
Changeover Relay is energized in HEAT when O/B switch is in the “B” position
Heat Relay
Fan
Relay
Optional
Optional Jumper for 
Single Stage Heat Pump
R
C
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G
W
Figure 3. Typical wiring diagram for two transformer single stage systems with NO safety circuits
TRANSFORMER
(Class II Current Limited)
Changeover
Relay*
Y
O/B
Compressor
Contactor
* Changeover Relay is energized in COOL when O/B switch is in the “O” position
Changeover Relay is energized in HEAT when O/B switch is in the “B” position
Heat Relay
Fan
Relay
Optional
Limit or
Safety
Switches
TWO COMMONS MUST
BE JUMPERED TOGETHER!
HOT
NEUTRAL
120 VAC
24 VAC
CUT AND
TAPE OFF!
If  safety  circuits  are  in 
only one of the systems, 
remove  the  transformer 
of  the  system  with 
NO 
safety circuits.
NOTE
Optional Jumper for 
Single Stage Heat Pump