D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1
EN | 117
Bosch Security Systems | 1/04 | 47775E
 
Provide for local programming by a D9133
Serial Interface Module.
Although not listed in this section, RPS still checks
for the RAM Passcode (see Section 2.7 RAM
Parameters
), Datalock Code, and the control panel
type to determine if this RAM session should
continue.
6.4.1
User Interface Modifications for
COMMAND 43
COMMAND 43 was modified to compensate for the
ability to communicate with RPS by a network path.
COMMAND 43’s structure is shown in Figure 5.
Figure 5: COMMAND 43 Flow Chart
1
2
9
10
11
3
9
10
6
11
11
4
7
5
8
1 -
COMMAND 43
2 -
Contact RAM?
3 -
RAM via Phone?
4 -
Seizes phone line and calls RPS
5 -
Answer now?
6 -
RAM by network?
7 -
Begins RPS session over the network
8 -
Seizes phone line and begins RPS session
9 -
[PREV]
10 - [NEXT]
11 - [ENT]
Pressing the [ESC] key while 
CONTACT RAM?
,
ANSWER NOW?
RAM VIA PHONE?
, or 
RAM VIA
NETWORK?
 is displaying exits the user to Idle Text.
The RAM via Phone? prompt shown in
Figure 5, if selected, contacts RAM by the
control panel phone line and not the
external modem. Users cannot initiate a
RAM session by the external modem. If you
are using an external modem, RAM
sessions can only be initiated by
programming Answer Armed and Answer
Disarmed (to a value greater than 0) or
setting RAM Line Monitor to Yes in
Section 6.4 SDI RAM Parameters.
Enable SDI RAM
Default:
Yes
Selection:
Yes or No
Yes
Enable RAM sessions over the SDI
bus.
No
Do not enable RAM sessions over the
SDI bus.
This item determines if the control panel allows RPS
communications over the SDI bus. This item must
be set to Yes if you plan on using the external
modem configuration, a private LAN or WAN, or
local RPS programming.
If the reset pin is in the locked position,
local RPS programming is allowed even if
this prompt is set to No.