D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1
EN | 125
Bosch Security Systems | 1/04 | 47775E
Once the control panel receives acknowledgement
from the central station, the control panel returns to
the normal Poll Rate (which, in this example is 120
seconds).
If more than one SDI Path is used, the control panel
handles them on a successive basis. For example, if
acknowledgement from SDI Path 1 is not received
within 10 seconds (using the previous example), the
control panel moves to SDI Path 2 to send its
Heartbeat Event (and subsequently waits for the ack)
before returning to SDI Path 1 to re-send its
heartbeat.
Beginning with firmware revision 6.20, if
Heartbeats are enabled and primary is an
SDI (or IP address) and the primary path
fails due to a heartbeat failure, then all
events should immediately go to the
backup path.
Entries are made in 1-second increments.
0101
0101
0101
Even though RPS and the D5200 allow
entries of 1 to 4, the control panel
interprets these entries as an entry of 5.
0101
0101
0101
5 minutes = 300 seconds
1 hour = 3600 seconds
12 hours = 43,200 seconds
18 hours = 64,800 seconds
Path # Ack Wait
Default:
13
Selection:
0, 5 seconds to 65535 seconds
0
The control panel does not look for
any acknowledgement from the central
station.
5 to 65535
The control panel waits this amount of
time to receive an acknowledgement
from the central station.
Determines how long the control panel waits for an
acknowledgement from the central station after a
Heartbeat Event (poll) or an actual event was
transmitted. This prompt is only applicable to SDI
transmitted events. Entries are made in 1-second
increments.
0101
0101
0101
Even though RPS and the D5200 allow
entries of 1 to 4, the control panel
interprets these entries as an entry of 5.
The value entered for Path # Ack Wait
Tone
 must not equal the time out entry
made in the RPS Account (see the RPS
Operation Manual, v2.9 or higher). Instead,
offset these values by 2 or 3. For example,
if your Path # Ack Wait time = 15,
program your Time Out value as 17 in the
RPS account.
Path # Retry Count
Default:
5
Selection:
0 to 255
0
COMM FAIL RG# SDI ### Events
are not generated.
1 to 255
COMM FAIL RG# SDI ### Events
are generated after the number of
retries are reached for a given SDI
path.
Determines how many times the control panel
resends the Heartbeat Event before declaring a path
failure and generating a COMM FAIL RG# SDI
### (RG # = 1 to 4, SDI ### = 88 for Path 1, 89
for Path 2, 90 for Path 3, 91 for Path 4) Event.
6.6
SDI RAM/Enhanced
Communications Configuration
This section provides the necessary prompts needed
for configuring the D9133TTL-E SDI-Ethernet
Interface Module when using it for SDI RAM
and/or SDI enhanced communication applications.
Baud Rate
Default:
9600
Selection:
300, 1200, 2400, 4800, 9600, 14.4 K
This item determines the communication baud rate
for the D9133TTL-E. Because the SDI bus
communicates at 9600 baud, keep this prompt also
at 9600 baud. Pressing the [SPACE] bar on the
D5200 toggles through the available options.
Do not change this value to any other
setting than 9600 baud.