D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS
EN | 86
Bosch Security Systems | 1/04 | 47775E
P## RlyResp Type
Default:
See 
Program Record Sheet
Selection:
Blank, 1 to 2
Blank
Point state does not affect the operation
of the corresponding relay.
1
Relay Follow Point: The relay
corresponding with this point activates
when the point is faulted to any off
normal condition. The relay
automatically resets when the point is
returned to normal.
2
Relay Latches: The relay
corresponding with this point latches
when the point goes into an alarm
condition. This relay provides a steady
output until the alarm is acknowledged
by a valid passcode then cleared from
alarm memory with an
acknowledgment at the command
center.
Use this option to cause a relay (1 to 127 for
D9412G; 1 to 64 for D7412G) to respond when a
corresponding point with the same number (1 to
127) is faulted. [This requires connecting D8129
OctoRelays to Zonex Bus 1 and/or Zonex Bus 2
(D9412G only). See address settings on the back of
the D9412G/D7412G Program Record Sheet (P/N:
47488)].
Point 128 is reserved for other use than an
actual point. Only the first 127 points can
have an associated relay. Relays are not
available for Points 129 to 247.
Do not use the Chg Relays? function to
toggle relays reserved for special
functions. Special function relays are Area
and Panel Wide Relay functions as well as
relays assigned to CC Entr Key Rly and
P## RlyResp Type.
P## Disp as Dvc
Default:
No
Selection:
Yes or No
Yes
Display 
CHECK DEVICE
 when this
point is off normal.
No
Do not display 
CHECK DEVICE
 when
this point is off normal.
Use this option to cause the command center to
display 
CHECK DEVICE
 once a point is off normal
or was acknowledged after going into alarm.
Use this function for devices with a dry
contact output which faults a point once
the device is in a trouble condition.
P## Local While Disarmed
Default:
See 
Program Record Sheet
Selection:
Yes or No
Yes
Suppress Alarm, Trouble and Restoral*
Reports from this point while the area
it is assigned to is disarmed.
No
Report events occurring from this
point while the area is disarmed.
*
Restoral Reports are still transmitted if the alarm,
trouble, or bypass (by Sked, RAM, or Swinger bypass)
condition occurred when the area disarmed, and the
point restored.
Use this option to allow a Controlled point (
P##
Type 1, 2, 3
), to report Alarms, Troubles, and
Restoral Reports only when the area is armed. This
prompt does not affect local annunciation.
Local While Disarmed suppresses all
reports from 24-hour points. Do not use
P## Type 0 for this prompt. Remember
that this only works for Disarmed points,
and a Type 0 is a 24-hour Always Armed
point. Instead, choose any type other than
0, and use a point response that reports
an alarm whether the point is armed or not.
For instance, P## Type 1 and P##
Response 9
 reports an alarm on an open
or a short (I) whether the area is armed or
not.
Local While Disarmed affects Keyswitch
points. This prompt suppresses keyswitch
(troubles/restorals) and D279
(alarms/troubles/restorals). Do not use this
parameter for these applications.
P## Local While Armed
Default:
No
Selection:
Yes or No
Yes
Suppress Alarm, Trouble and Restoral*
Reports from this point while the area
it is assigned to is armed.
No
Report events occurring from this
point while the area is armed.