Operation
4.1
Door Release Application
The D9210B can be used for door
release functions. When used in
this configuration, the strike relay
contacts must be supervised. This
can be accomplished with the use
of an end-of-line relay commonly
used for smoke detectors.
Connecting the D9210B for this
application is shown in Figure 6.
Program Point Index in the
POINTS handler as Supervisory
with Point Response as [A]
Supervisory on Open and Trouble
on Short
.
The power supply, end-of-line
relay, and the D9210B must be in
the same enclosure or adjacent
enclosures connected via conduit
not longer than 20 ft. (6 m).
-
D9210B
AUX POWER
UL Listed for Fire
POPIT
RELAY
DOOR A
MAGNETIC
DOOR HOLDER
(+)
(-)
1
PWR +
2
LCKN/C
3
LCKCOM
4
LCKN/O
6
SDIA
8
T +
9
ZNCOM
5
COM
7
SDIB
10
ZN +
11
RTE
12
COM
Figure 6: D9210B Door Release Application Connections
Note: 