APC Fluid Cooler 57MBH@20TD, 10GPM, 8 Feeds, 400/3/50 ACFC75257 User Manual

Product codes
ACFC75257
Page of 56
InRow RD Technical Data Manual
4
Standard Features
Cabinet
The frame is constructed of 16 gauge 
formed steel for maximum strength. 
The cabinet is serviceable from the 
front and rear. All exterior panels and 
corner posts on the frame are powder 
coated for durability and an attractive 
finish. The front and rear exterior 
panels are constructed of 18 gauge 
perforated steel with 69.5% open free 
area. All panels, which include a key 
latch for safety and security, allow 
easy access and removal. Insulation 
(ACRD100 and ACRD200 series 
only) is 80.1 kg/m
(5 lb/ft
3
)
 
density 
and complies with ASTM E84 rating 
of 25/50.
Shutdown Input/Alarm 
Output
The unit provides one field connec-
tion input for remote shutdown and 
one field connection alarm output.
Variable Speed Fans
Each unit is equipped with variable 
speed fans to allow for varying heat 
loads. In order to provide uniform 
airflow over the cooling coil, the fans 
provide a draw-through air pattern. 
The ACRD100 and ACRD200 series 
units are equipped with six direct 
drive fan modules. These fans are 
easily replaceable while the unit is in 
operation.  The ACRD500 series is 
equipped with two backward 
inclined, direct drive fans. 
Bay Kit-InRow RD/
NetShelter SX
Baying kits made of 16 gauge steel 
enable baying the InRow RD to APC 
NetShelter enclosures.
Counterflow Cooling Coil/
Condensate Pan
Designed for high sensible heat 
ratios, the coil is constructed with 
copper tubes, raised lance type alu-
minum fins, and 18 gauge galvanized 
steel end plates. Coil headers are 
equipped with anti-drip shields in the 
event of condensation. The conden-
sate pan is thermal formed non-
ferrous material, and is sloped for 
positive drainage to provide higher 
indoor air quality.
Filters
Filtration of conditioned air is 
extremely vital to maintaining the 
clean, particle-free environment 
required by electrical equipment. Fil-
ters are easily replaceable from the 
rear of the unit. The ACRD100 and 
200 series systems use greater-than 
20% efficiency ASHRAE 52.1, 12.7 
mm (1/2 in) washable filters that 
meet HF-1 standards for electronics 
(MERV 1 per ASHRAE 52.2). The 
ACRD500 series system uses a 30% 
efficient, 102 mm (4 in), deep load-
ing, pleated filter (MERV 8 per 
ASHRAE 52.2, EN779 G4). 
Selectable Top or Bottom 
Piping Connections
The unit includes both top and bot-
tom piping connections. All 
ACRD100 and ACRD500 series con-
nections utilize Roto-Lok fittings for 
ease of installation and service. The 
ACRD200 series uses union 
connectors.
Network Management Card
The Network Management Card 
(NMC) allows communication with 
the Local Area Network (LAN). In 
addition, the NMC permits multi-
level access to monitoring, control, 
and event notification features over 
the building network.
Condensate Pump
ACRD100 and ACRD200 series:
Two pumps are factory wired and 
piped (in parallel) internally to the 
condensate drain pan. Acting 
together, the pumps are capable of 
pumping 9.8 l/hr (2.6 g/hr) against 
head pressures of up to 50 ft (15.2 m) 
of total run. Of that run, 16 ft (4.9 m) 
can be vertical lift as measured from 
floor level. Dual floats are included 
with the unit. One float is used for 
condensate pump control, and the 
other float generates a condensate 
pump failure alarm. The InRow RD 
can be set to either continue running 
in an alarm condition or shut down to 
prevent condensate pan overflow.
ACRD500 series:
The single condensate pump is fac-
tory wired and piped internally to the 
condensate drain pan. The pump is 
capable of pumping a maximum of 
18 m (60 ft) at 32 l/h (8.45 g/hr), 
which may include a maximum lift of 
3.5 m (11.5 ft) as measured from 
floor level. Dual floats are included 
with the unit. One float is used for 
condensate pump control, and the 
other float generates a condensate 
pump failure alarm to prevent 
condensate pan overflow.
Remote Temperature 
Sensors
To control the unit based on rack inlet 
temperature, remote temperature sen-
sors are provided. The ACRD100 
and ACRD200 series units come 
equipped with one temperature sen-
sor, and the ACRD500 series units 
come equipped with three. These 
sensors measure temperature at a 
point 4 m (13 ft) from the connection 
inside the InRow RD unit. These sen-
sors are used for remote placement in 
the field on an adjacent IT rack.