White Rodgers 50A55-474 User Manual

Page of 8
2
SPECIFICATIONS
ELECTRICAL RATINGS [@ 77
°
F (25
°
C)]:
Input Voltage:  25 VAC 50/60 Hz
Max. Input Current @ 25 VAC:  0.45 amp
Relay Load Ratings:
Valve Relay:  1.5 amp @ 25 VAC 50/60 Hz 0.6 pf
Ignitor Relay:  6.0 amp @ 120 VAC 50/60 Hz
(resistive)
Flame Current Requirements:
Minimum current to insure flame detection:  1 
µ
a DC*
Maximum current for non-detection: 0.1 
µ
a DC*
Maximum allowable leakage resistance: 100 M ohms
* Measured with a DC microammeter in the flame probe
lead
OPERATING TEMPERATURE RANGE:
-40
°
 to 175
°
F (-40
°
 to 80
°
C)
HUMIDITY RANGE:
5% to 93% relative humidity (non-condensing)
MOUNTING:
Surface mount multipoise
Timing Specs:  (@ 60 Hz**)
maximum
Flame Establishing Time:
0.8 sec
Flame Failure Response Time:
2.0 sec
** At 50 Hz, all timing specifications should be increased
by 20%.
Gases Approved: Natural, Manufactured, Mixed, Liquified
Petroleum, and LP Gas Air Mixtures are all approved for
use.
TIMING SPECIFICATIONS
(All times are in seconds, unless noted otherwise)
* These times will vary depending on option switch 
position. The control is factory-set at 0 sec. delay 
to cool off and 100 sec. delay to heat off. See 
OPERATION section for further information.
 This time will vary depending on the condition of 
the jumper. With the jumper installed, the delay-to-
cool-off is set at 0 seconds. To obtain an 80-
second delay-to-cool-off, clip the jumper wire and 
separate the jumper legs.
PRE-PURGE
TRIAL FOR IGNITION 
PERIOD
IGNITION ACTIVATION 
PERIOD
RETRIES
VALVE SEQUENCE 
PERIOD
INTERPURGE
POST-PURGE
LOCKOUT TIME
DELAY TO HEAT ON
DELAY TO HEAT OFF
DELAY TO COOL ON
DELAY TO COOL OFF
MINIMUM IGNITOR 
WARM-UP
MAXIMUM IGNITOR 
WARM-UP
INITIAL IGNITOR 
WARM-UP (1st 64 
attempts)
HUMIDIFIER
ELECTRONIC AIR 
CLEANER
0
4
1
2 times
12
60
5
300
45
60/100/ 
140/180*
2
0/80*
11
21
17
YES
YES
50A55-474
0
4
1
2 times
12
60
5
300
45
100 
2
0/80
11
21
17
NO
NO
50A55-571