White Rodgers 1F80-24 Installation Instruction

Page of 6
3
CHECK THERMOSTAT OPERATION
If at any time during testing your system does not operate
properly, contact a qualified serviceperson.
Fan Operation
If your system does not have a G terminal connection, skip to
Heating System.
1. Turn on power to the system.
2. Move FAN switch to ON position. The blower should begin
to operate.
RH
Y
THERMOSTAT
SYSTEM
G
W
Figure 3. Typical wiring diagram for heating only,
2-wire, single transformer systems or millivolt systems
Heating
System
RC
O
B
24 VAC Transformer
or
Thermopile
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G
W
Figure 7. Typical wiring diagram for
heat/cool, 4-wire, single transformer systems
TRANSFORMER
Heating
System
Fan
Relay
Cooling
System
RC
JUMPER
WIRE
RED jumper wire (provided 
with thermostat) must be 
connected between thermo-
stat's RH and RC terminals 
for proper thermostat oper-
ation with this system.
NOTE
O
B
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G
W
Figure 9. Typical wiring diagram for
heat pump with cool active reversing valve
TRANSFORMER
Reversing
Valve*
RC
O
B
JUMPER
WIRE
Compressor
Contactor
JUMPER
WIRE
* Reversing valve is energized when the
   system switch is in the COOL position
Fan
Relay
R
W
B
W
R
Thermostat
3-wire Series 10
Primary Control
(located at furnace)
Add jumper wire
(not provided with thermostat)
Figure 4. Typical wiring diagram for
3-wire SERIES 10 heating systems
Furnace
Jumper wire must be 
added between R and B 
terminals on the primary 
control (jumper wire not 
provided with thermostat).
NOTE
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G
W
Figure 5. Typical wiring diagram for
heat only,  3-wire, single transformer systems
TRANSFORMER
Heating
System
Fan
Relay
Y
RC
JUMPER
WIRE
RED jumper wire (provided 
with thermostat) must be 
connected between thermo-
stat's RH and RC terminals 
for proper thermostat oper-
ation with this system.
NOTE
O
B
RH
Y
24 VAC
120 VAC
Hot
Neutral
TRANSFORMER
THERMOSTAT
SYSTEM
G
W
Figure 6. Typical wiring diagram for
cool only, 3-wire, single transformer systems
Cooling
System
Fan
Relay
RC
O
B
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G
W
Figure 8. Typical wiring diagram for
heat/cool, 5-wire, two-transformer systems
HEATING TRANSFORMER
Heating
System
Fan
Relay
Cooling
System
RC
24 VAC
120 VAC
Hot
Neutral
COOLING TRANSFORMER
O
B
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G
W
Figure 10. Typical wiring diagram for
heat pump with heat active reversing valve
TRANSFORMER
Reversing
Valve*
RC
O
B
JUMPER
WIRE
Compressor
Contactor
JUMPER
WIRE
* Reversing valve is energized when the
   system switch is in the HEAT position
Fan
Relay
3. Move FAN switch to AUTO position. The blower should stop
immediately.
Heating System
1. Move SYSTEM switch to HEAT position. If the heating
system has a standing pilot, be sure to light it.
2. Press 
 to adjust thermostat setting above room tempera-
ture. The heating system should begin to operate.
3. Press 
 to adjust temperature setting below room tempera-
ture. The heating system should stop operating.