Bosch Appliances Video Game Controller d9412gv3 User Manual

Page of 154
D9412GV3/D7412GV3 | Program Entry Guide | 3.0  Points 
EN | 103 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
P### Relay 
Default: 
Refer to the program record sheet 
Selection:  0 to 8 
 
Use this option to activate a relay when the point is 
faulted. Refer to Table 28
 
 
Relays do not activate for Fire 
Supervisory or Non-Fire Supervisory 
points. 
 
Table 28: P### Relay Codes/Relays 
 
Faults Relay 
Relay Code 
D8129 on  
Zonex Bus 2  
for D9412GV3* 
D8129 on  
Zonex Bus 1  
for D7412GV3* 
73 
2 74  10 
75 
11 
4 76  12 
77 
13 
6 78  14 
79 
15 
8 80  16 
* Address setting = 1 (on), 2 (off), 3 (on), 4 (on) 
 
 
 
Do not assign a relay to Invisible points. 
To avoid activating one of the associated 
relays, program this prompt  
as 0. 
 
 
Two relays can activate when this point 
enters into alarm if the P## Relay 
Response Type
 for this point is 
programmed. 
Use these codes to activate relays on the 
D8129 OctoRelay (or C8137 Transmitter 
Interface). You can assign the same code 
to several points providing a summary 
zone alarm output. When the point enters 
into alarm, the relay activates. When the 
alarm is acknowledged and is no longer 
scrolling in the keypad display, the relay 
resets. 
 
P### Point Text 
Default: 
Refer to the program record sheet 
Selection:  Up to sixteen alphanumeric 
characters 
Enter alphabetic characters (A to Z) in capital letters. 
Enter up to sixteen characters of text to describe the 
point. This point text is shown at keypads, if the point 
is programmed as visible, and sent to the D6500 or 
D6600 when transmitting in Modem IIIa
2
 format (if it is 
a reporting point). 
Include the point number in custom point text. This 
helps the user when viewing events, creating 
bypasses, and so on. It can also simplify 
troubleshooting.