D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 12 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
2.0  Panel and Area Wide 
Parameters 
This section has twelve programming categories:  
  Phone 
  Phone Parameters 
  Routing 
  Area Parameters 
  Power Supervision 
  Printer Parameters 
  RPS Parameters 
  Miscellaneous 
  Area Parameters 
  Keypad 
  User Interface 
  Function List 
  Relay Parameters. 
2.1 Phone 
The control panel can dial as many as four different 
telephone numbers when sending event reports. 
Refer to Section 2.3 Routing on page 17 for 
information about event report routing and 
communication protocols. 
 
 
When using PSTN telephone lines, 
program two telephone numbers to 
meet UL 864 requirements. 
 
Phone #  
Default: 
Blank 
Selection:  Up to 24 characters 
0 to 9 
Numbers 0 through 9 
C 3-sec 
pause 
7-sec dial-tone detection 
# or * 
Used for the same purpose as 
pressing this key on a telephone 
keypad when manually dialing. For 
example, an asterisk (*) may be 
needed to access your long distance 
service. Do not use these characters 
when pulse dialing. 
Blank 
Control panel dials no phone number. 
Programming this item Blank does 
not disable phone routing. To disable 
reporting to this phone, refer to 
Section 2.3 Routing on page 17. 
This is the telephone number the control panel dials to 
contact the central station receiver when sending 
event reports. This number is Phone 1 referred to in 
the prompts in Section 2.3 Routing on page 17. 
The control panel waits for a break in the dial tone 
after dialing the first digit. If the control panel must dial 
a digit (for example, 9) to access an outside line, place 
a C before the phone number. The control panel waits 
2 sec and does not wait for the dial tone break. 
The control panel is programmed with a 7-sec dial 
tone detect period. When a dial tone is detected or the 
waiting period ends, the control panel begins to dial. 
To extend the dial tone detect period, place a D before 
the phone number. To insert a pause during or after 
dialing, use C in the number sequence. For example, 
if the control panel hangs up before it hears the 
Modem IIIa
2
 ACK tone from the D6500 or D6600, 
program extra Cs after the phone number. The control 
panel waits on line for two extra seconds for each C 
programmed. 
Enter up to 24 of the characters shown in the Phone # 
table to define dialing characteristics. 
For SIA CP-01 Compliance 
Call Waiting Disable 
If the telephone system at the installation site uses the 
Call Waiting feature, ensure that the primary 
telephone reporting number is programmed to disable 
Call Waiting.