D9412GV3/D7412GV3 | Program Entry Guide | 6.0  ACCESS CONTROL 
EN | 143 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
 
 
This command unlocks the door 
regardless of the armed state. 
 
 
Each fire alarm that is generated causes 
a Door Unlocked – Automatic Event. 
 
D# Disarm on Open? 
Default: 
Yes 
Selection: 
Yes or No 
Yes 
The area disarms only after the door 
is opened for a user with a valid 
disarm level. 
No 
The area disarms whether or not the 
door is opened as soon as a user 
with a valid disarm level presents a 
valid token or card. 
Use this program item to determine if the door needs 
to be physically opened before disarming the area 
upon a valid access request. The user initiating the 
access request needs access levels that allow 
disarming with ID. 
D# Card Type 
Default: 
Selection: 
0 to 3 
Card format is 26-bit Wiegand. 
Do not use. Card format is 37-bit 
fidelity.  
This item must be kept to a value of 0 (26 bit 
Wiegand format). 
 
6.2 Strike 
Profile 
This programming category is used to create a 
specific door profile for: 
  Strike and shunt times. 
  Extending strike and shunt times if a door is left 
open. 
  Resetting the strike when the door opens. 
Door # 
Default: 
Selection: 
1 to 8 
Enter the door you are programming. 
D# Strike Time 
Default: 
10 sec 
Selection: 
1 sec to 240 sec 
Strike Time is not programmed for 
this door. 
1 to 240 
The strike activates for the amount 
of time programmed. 
Enter the amount of time the door controller toggles 
the relay output to activate the door strike. When the 
door strike is activated, the user can open the door. 
The strike activates for a valid token, RTE, REX, and 
the keypad CYCLE DOOR? function. 
D# Shunt Time 
Default: 
10 sec 
Selection: 
0 to 240 sec 
Shunt Time is not programmed for 
this door. 
1 to 240 
The shunt activates for the amount 
of time programmed. 
Enter the amount of time that the Door point is 
shunted to allow a user to open the door. The 
duration of time should be sufficient so that the 
opened door does not cause the point to enter into a 
trouble, alarm, or faulted condition.