D9412GV3/D7412GV3 | Program Entry Guide | 6.0  ACCESS CONTROL 
EN | 144 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
D# Buzz Time 
Default: 
2 sec 
Selection: 
0 to 240 sec 
Buzz Time is not programmed for 
this door. 
1 to 240 
The buzzer sounds for the amount 
of time programmed. 
Enter the amount of time the buzzer output sounds to 
notify the user that the strike was activated and the 
door is ready to open. The buzzer stops as soon as 
the door is opened. 
 
A separate buzzer is required. Many 
readers have an internal buzzer that is 
not affected by Buzz Time. 
D# Extend Time 
Default: 
10 
Selection: 
0 to 30 sec 
Enter the amount of time that strike, buzz, and shunt 
activation is prolonged if a door is left open and the 
shunt time expires. At the end of the programmed 
extend time, the buzzer continues to buzz until the 
door closes. If programmed, the point assigned to the 
door indicates a trouble, alarm, or fault at the keypad. 
 
The CLOSE DOOR # display on keypad 
does not activate if D# Extend Time is 
set to 0. 
 
 
Regardless of how the Door point is 
programmed, the system generates a 
Trouble Door Left Open Event while the 
system is disarmed, and an Alarm Door 
Left Open Event if the system is armed 
and the door is held open beyond Extend 
Time. Door Closed - Restoral Events are 
generated after the door is held open 
past Extend Time and the door returns to 
normal. 
D# Deactivate On Open? 
Default: 
Yes 
Selection: 
Yes or No 
Yes 
Strike deactivates when the door is 
opened after a valid Access Granted 
request. 
No 
Strike remains activated for the 
amount of the programmed strike 
time whether door is opened or 
closed. 
Determines if the strike deactivates immediately upon 
physically opening the door. 
 
In order for this function to work, a point 
needs to be assigned to the door. 
 
 
To Reduce False Alarms, maintain D# 
Deactivate on Open?
 as the default 
(Yes). This helps prevent the door from 
bouncing open and causing a false 
alarm. 
 
D# RTE Shunt Only? 
Default: 
No 
Selection: 
Yes or No 
Yes 
Programmed shunt time activates 
so door can be manually opened. 
No 
RTE automatically activates the 
programmed strike and shunt time. 
Use this program item to disable the strike, but still 
activate the programmed shunt time at a Request to 
Enter (RTE) area. 
 
Use this parameter when a user can 
open a door manually without relying on 
a token or card to activate the strike 
(such as with a push bar). 
 
 
When RTE Shunt Only is Yes, RTE 
Events are not logged, reported, or 
printed.