D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 21 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
2.3.9 Route 
Group 
Categories
 
Fire Reports 
 
 
To meet UL 864 requirements for 
Central Station and Remote Station 
applications, enable Fire Reports
 
Selecting Yes enables a report to be sent when the 
event occurs. 
Table 9:  Fire Reports 
 
Report Selections 
Report 
Description 
R# Fire Alarm  Yes, No 
Fire Event 
R# Fire 
Restore 
(Alarm) 
Yes, No 
Fire restoral from 
alarm 
R# Fire 
Missing 
Yes, No 
Missing Fire point 
R# Fire 
Trouble 
Yes, No 
Fire trouble 
R# Fire 
Supervis 
Yes, No 
Fire supervision 
R# Fire 
Restore 
(T/M/S) 
Yes, No 
Fire restoral from 
trouble, missing, or 
bypass 
R# Fire 
Cancel 
Yes, No 
Canceled fire alarm 
R# Fire Sup 
Miss 
Yes, No 
Fire supervisory 
missing 
R# Fire Supv 
Rest 
Yes, No 
Restorals from Fire 
Supervision 
 
Burglar Reports 
Select Yes to send a report when the event occurs. 
Refer to Table 10 on page 21. 
Table 10: Burglar Reports 
 
Report Selections  Report Description 
R# Alarm  
Yes, No 
Burglar Alarm Event 
R# Burg 
Restore 
Yes, No 
Non-fire restoral from 
trouble, missing, or 
supervisory 
R# Duress 
Yes, No 
Duress 
R# Missing 
Alarm 
Yes, No Missing 
Alarm 
point 
R# Usr Code 
Tmpr 
Yes, No 
User code tamper 
R# Trouble 
Report 
Yes, No Trouble 
Event 
R# Missing 
Trbl 
Yes, No 
Missing Trouble 
Event 
R# Non Fire 
Suprv 
Yes, No 
Non-fire Supervision 
Event 
R# Pt Bus 
Fail 
Yes, No 
Point bus failure 
R# Pt Bus 
Rstl 
Yes, No 
Restoral of point bus 
after failure 
R# Non Fire 
Cncl 
Yes, No 
Canceled non-fire 
alarm 
R# Alarm 
Restore 
Yes, No 
Non-fire restoral from 
alarm 
R# Sup 
Missing 
Yes, No 
Supervisory missing 
R# Unverified 
Evt
 
 
Yes, No 
Unverified Events for 
Cross Points 
 
 
R# Unverified Evt is sent when a single 
point programmed in Cross Point Group 
faults into an alarm condition, then 
restores before the Cross Point Time 
elapses.  
R# Unverified Evt encompasses both 
Fire and Non-fire points, but is not related 
to the A# Verify Time used for smoke 
detectors. 
 
The GV3 Series control panels log a 
Ground Fault Event as Trouble Point 256. 
 
 
Restoral Reports are not sent if the 
control panel resets after a point is 
bypassed and then unbypassed. This is 
true for both Fire and Non-fire points.