D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 52 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
CC# Scope 
Default: 
Refer to the program record sheet 
Selection:  Panel Wide, Custom, No Keypad, 
Area, and Account 
Panel 
Wide 
A panel-wide keypad can view 
information and perform Arming and 
Disarming functions for all areas in 
the control panel. A panel-wide 
keypad can cross account 
boundaries. This is normally used 
with a master area. 
Account 
An Account keypad can view 
information, and perform Arming and 
Disarming functions for all areas with 
the same A# Account Number, in 
Area Parameters. This is normally 
used for an associate area. 
Area 
An area keypad is restricted to 
viewing information and Arming or 
Disarming functions for the area to 
which it is assigned. 
Custom 
A custom keypad shows information 
and allows arming and disarming for 
specific areas you select. (This option 
is not available through Keypad 
Programming.) 
No 
Keypad 
No keypad installed at this address. 
CALL FOR SERVICE display shows, 
indicating the control panel is not 
polling this address. 
This program item is used to define the areas 
affected when an arming command is executed on 
this keypad, the areas this keypad can view, and the 
areas to which this keypad can move. 
 
In applications where keypads include 
more than one area, active alarms in 
remote areas must be acknowledged 
before arming or disarming the local area. 
 
 
The following prompt is visible only when 
you program CC## Scope to Custom. If 
you change the keypad scope selection 
to Custom from Panel Wide, Account, or 
Area, the settings from the previous CC# 
Scope
 selection become the default 
settings for the custom parameters in 
CC# A1 [through A#] in Scope. Before 
exiting from a custom program, check 
each area and ensure that it is enabled 
and disabled correctly. 
 
CC# A1 [through A#] in Scope 
Default: 
Refer to the preceding important 
note  
Selection:  Yes or No 
Yes 
Include this area in the scope of this 
keypad. 
No 
Do not include this area in the scope 
of this keypad. 
Determines whether any of the areas and doors are 
included in the scope of this keypad for viewing 
status, arming or disarming, and controlling doors 
from the keypad. 
Keypad Programming of CC# Scope 
D1255 
1.  Refer to Figure 1 on page 7 to access Keypad 
Programming and navigate to the COMMAND 
CENTER 
option.  
2.  Press [ENT]. The CC NUM 1 – 16 option shows. 
3.  Enter the keypad number you wish to configure 
and press [ENT]. The keypad reads CC# 
SCOPE
, and then the current configuration (for 
example, PANEL WIDE). 
4.  To change the configuration, press [ENT] when 
the current configuration shows, and then press 
[NEXT] or [PREV] to scroll through the options, 
as listed in CC# Scope on page 52 .  
5.  When the keypad reads the desired configuration 
option, press [ENT] to select it. 
When the keypad reads PARAMETER SAVED
your selection has been configured. 
 
D1260 
1.  Refer to Figure 2 on page 8 to access Keypad 
Programming and navigate to the Command 
Center 
option.  
2.  Press [ENTER]. The CC Num 1 – 16 option 
shows. 
3.  Enter the keypad number you wish to configure 
and press [ENT]. The keypad reads CC# Scope
and then the current configuration (for example, 
Panel Wide). 
4.  To change the configuration, press the Edit 
softkey, and then press the Next or Previous 
sofkeys to scroll through the options, as listed in 
CC# Scope on page 52 .  
5.  When the keypad reads the desired configuration 
option, Save to select it. 
When the keypad reads Parameter Saved, your 