D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 61 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
Instant arms all perimeter points with point response 
that starts an instant alarm (refer to P## Pt 
Response
 in Section 3.2 Point Responses on page 
91) in the area where the keypad is assigned. Entry 
and exit delays are not provided with this arming 
function. This function causes a Perimeter Delay 
point to act as a Perimeter Instant point. 
For SIA CP-01 Compliance 
 
This feature is not allowed in SIA CP-01 
compliant installations. 
Perimeter Delay 
Default: 
Selection: 
-, E, or P 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
Perimeter Delay 
Arm 
[COMMAND][3] 
Delay arms all Perimeter points in the area where the 
keypad is assigned. Entry and exit delays are 
provided with this Arming function. This function does 
not cause a Perimeter Instant point to act as a Delay 
point. 
Watch Mode 
Default: 
Selection: 
-, E, or P 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
6 Watch 
Mode 
[COMMAND][6] 
This function informs you when a perimeter point or 
interior point that is programmed as P## Watch 
Point
 is faulted while the area is disarmed. Interior 
points do not emit a Watch Tone if the area is 
perimeter armed. This function provides keypad 
audible or visual and optional relay activation (refer to 
A # Watch Mode in Section 2.12.1 Area Relays on 
page 79). 
 
Perimeter Partial 
Default: 
Selection:  -, E, or P 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
Perimeter Partial 
Arm 
[COMMAND][8] 
Use this function to arm normal perimeter points and 
force-bypass faulted perimeter points, regardless of 
their P## Bypassable setting. When these force-
bypassed perimeter points return to normal, they 
automatically return to service, even if P## FA 
Returnable is set to No. 
Perimeter Partial arming has entry and exit delays. 
 
Perimeter Partial ignores the A# Force 
Arm/Bypass Max
 entry in Section 2.8 
Area Parameters 
on page 36. 
 
 
Local Only Reporting: No Closing 
Report is sent to the central station, but a 
Perimeter Delay Closing Event is 
generated in the event log. 
 
View Area Stat 
Default: 
Selection: 
-, E, or P 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
View Area Status 
(Menu function 
only) 
Use this function to view the armed status of all areas 
within the scope of the keypad assigned to this area. 
The armed states include A# AREA # IS OFF 
(disarmed), A# AREA # IS ON (master delay armed), 
ALL ON INSTANT (master instant armed), and AREA 
# PERIMETER ON (perimeter instant armed or 
perimeter delay armed). All area types, master, 
associate, regular, and shared can be viewed using 
this function.