D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 80 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
 
 
When sharing one relay to reset sensors 
in two or more areas, you must program 
the following. Failure to do so causes 
TROUBLE PT ### for all point types 
programmed as P## Resettable
  CC # Scope must include all areas 
that share the relay. 
  L## Reset Sensors authority must be 
assigned to the passcode that 
activates the COMMAND 47 or Reset 
Sensor function. 
  A# Verify Time must be the same 
number of seconds for all areas that 
share the relay. 
 
 
To meet UL 864 requirements, set A# 
Reset Sensors
 to a value other than 0. 
 
A# Fail to Close 
Default: 
Selection:  0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
This relay activates when the Closing Window 
expires for the specified area. It remains active until 
midnight, another Closing Window starts, or the 
control panel resets, whichever occurs first. When 
Perimeter Relay (refer to page 139) is set to Yes
the A# Fail to Close prompt becomes A# Perimeter 
Relay
A# Force Armed 
Default: 
Selection:  0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
This relay activates when this area is Force Armed. It 
remains active until the area disarms or the control 
panel resets. 
 
If Force Bypassing is required during 
Perimeter Arming, this relay does not 
activate. 
A# Watch Mode 
Default: 
Selection:  0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
This relay activates when a Controlled point 
programmed for P## Watch Point is faulted in the 
specified area while the area is in Watch Mode and 
the point is not armed. It remains active for 2 sec 
after each point is faulted. 
A# Area Armed 
Default: 
Selection:  0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
This relay activates when the specified area becomes 
Master Armed. The exit delay must expire before the 
relay activates. The relay remains active until the 
area disarms. It does not deactivate during the entry 
delay time. 
If multiple areas use the same relay, the relay 
activates when all areas are armed. It deactivates 
when the first area disarms. 
The A# Area Armed relay function can provide visual 
feedback at a key switch station. Attach a LED to the 
output of a D8129 Module programmed for this 
function. 
A# Area Fault 
Default: 
Selection: 
0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
Activates whenever a controlled (P## Type 1, 2, 3 
only) Perimeter or Interior point is faulted. The relay 
remains active until all Perimeter and Interior points 
in the area are normal. 
 
Keyswitch area armed status with 
LEDs:
 Use a D8129 Module and connect 
an LED to indicate that the area is not 
ready to arm.