D9412GV3/D7412GV3 | Program Entry Guide | 1.0  Introduction 
EN | 9 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
1.3 
Guide to UL 864 Programming Requirements 
This section identifies the programming requirements you must make in order to comply with UL 864 
Commercial Fire applications. 
 
 
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER 
INVOLVED PARTIES 
This product incorporates field-programmable software. In order for the product to comply with the 
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 
you must limit certain programming features or options to specific values. Refer to Table 3
 
Table 3:  UL 864 Programming Requirements 
 
Product Feature/Option  Permitted in 
UL 864? (Y/N) 
Possible Settings  Settings Permitted in  
UL 864 
Refer to 
Page: 
If using two phone lines: 
Phone 1 through 4 
Yes 
24 characters 
Program a valid phone 
number 
12  
Phone Supervision 
Yes 
0 to 240 sec 
10 to 200 sec 
16 
Alarm On Fail 
No 
Yes / No 
Set to No 
16 
Buzz On Fail 
Yes 
Yes / No 
Set to Yes 
16 
Two Phone Lines 
Yes 
Yes / No 
Set to Yes when using 
PSTN communications. 
16 
Expand Test Report 
Yes 
Yes/No 
Set to Yes 17 
Fire Reports 
Yes 
Yes / No 
Set to Yes 
21 
R# Fire Supervisory 
Missing 
Required 
Yes/No 
Set to Yes 
21 (Table 9
Test Reports 
Yes 
Yes / No 
Set to Yes 
22 
AC Fail Report 
Yes 
Yes / No 
Set to Yes 
23 (Table 13
AC Restoral Report 
Yes 
Yes / No 
Set to Yes 
23 (Table 13
Battery Missing Report 
Yes 
Yes / No 
Set to Yes 
23 (Table 13
Low Battery Report 
Yes 
Yes / No 
Set to Yes 
23 (Table 13
Battery Restoral Report 
Yes 
Yes / No 
Set to Yes 
23 (Table 13
R# Service Start Report 
Required 
Yes / No 
Set to Yes 
26 (Table 17
R# Service End Report 
Required 
Yes / No 
Set to Yes 
26 (Table 17
R# Fire Walk St Report 
Required 
Yes / No 
Set to Yes 
26 (Table 17
R# Fire Walk End Report  Required 
Yes / No 
Set to Yes 
26 (Table 17
R# Walk Test St Report 
Required 
Yes / No 
Set to Yes 
26 (Table 17
R# Walk Test End Report  Required 
Yes / No 
Set to Yes 
26 (Table 17
AC Fail Time 
Yes 
1:00 to 90:00 min 
Enter 1:00 
29 
AC Fail Display 
Yes 
10 to 300 sec 
10 to 200 sec 
29 
AC Tag Along 
Yes 
Yes / No 
Set to Yes 
29 
AC/Battery Buzz 
Yes 
Yes / No 
Set to Yes 
30