D9412GV3/D7412GV3 | Program Entry Guide | 3.0  Points 
EN | 90 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
 
P ## Type 
Selection 
Description 
D279 (O/C Non-Priority): The D279 provides point arming and disarming independent of the 
area arm state. A non-priority D279 point arm state does not affect the area arm state. Point 
Response
 must be programmed 1. Local bells are silenced through the keypad. For bell 
control at the D279, use P## Type 8
Open the W1 jumper on the D279 to send Point Opening and Point Closing Reports. If the 
D279’s W1 jumper is closed, no Open or Close Report is sent, regardless of control panel 
programming. 
   Normal: 
The point is armed and sends a Point Closing Report. Point Closing Report is 
not sent if Local Armed is Yes
  Open: 
The point is disarmed and sends a Point Opening Report. A Point Opening 
Report is not sent if Local Armed is Yes
7* 
  Short: 
A short is an alarm when the point is armed. A short is a trouble when the 
point is disarmed. Alarm and Restoral Reports are not sent if Local 
Disarmed
 is Yes
D279 (O/C Priority): The D279 provides point arming and disarming independent of the 
area’s arming state. A priority D279 point must be armed before an area can be armed. 
Program Point Response as 2. 
Open the W1 jumper on the D279 to send area Opening and Closing Reports as programmed 
in Area Parameters and to provide bell control. If the D279’s W1 jumper is closed, no Area 
Open or Area Close Report is sent, and alarm bells can only be silenced from a keypad, no 
matter how the control panel is programmed. 
  Normal: 
When this point changes from open to normal, the area arms. 
  Open: 
The area is disarmed. The alarm bell silences if an alarm occurred while the 
area was armed. 
8* 
  Short: 
A short is a trouble while the area is disarmed. A short is an alarm while the 
area is armed. When this point changes from shorted to normal or open, it 
restores. 
9* 
Easikey: This point is programmed for access. Program Point Response as 1. If the system 
is Master Armed or Perimeter Armed (with or without delays), presenting a valid token to the 
Easikey reader shorts the point and disarms its assigned area. Presenting a valid token in a 
disarmed state does not clear trouble or alarm memory or rearm the area. 
11 
Aux AC Supervision: This point type monitors the AC power of an auxiliary power supply. 
When the point is in an off-normal state, the control panel waits for the time programmed in 
AC Fail Time before generating a Point Trouble. If P## Fire Point is set to Yes, the off-
normal condition results in a Fire Trouble. This point type does not use P## Point Response
therefore, no alarm condition occurs. If this point type is bypassed, 24 HOUR PT BYPASSED 
is shown on the keypads. 
*  Keyswitch Points. Special rules apply to points used for Keyswitch functions. These special point types do not 
respond the same way to the point response entry as Point Types 1, 2, and 3.