Bosch Appliances Video Game Controller d9412gv3 User Manual

Page of 154
D9412GV3/D7412GV3 | Program Entry Guide | 3.0  Points 
EN | 94 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
 
When a point programmed for P## Silent 
Bell
 is faulted, the timer for the A# Burg 
Time
 starts, even though the bell is not 
yet ringing. As much as 3 min can elapse 
before the second attempt fails. Ensure 
that A# Burg Time is programmed to 
provide the amount of bell time you need, 
minus the additional 3 min that might 
elapse before the bell actually begins to 
ring. 
P## Invisible Point 
Default: 
Refer to the program record sheet 
Selection: 
Yes or No 
Yes 
Keypads do not display alarm 
activity from this point. 
No 
Activity from this point is visible at 
the keypads. 
 
 
To meet UL 864 requirements, set this 
parameter to No
 
Use this option to determine whether the point 
appears in the keypad display upon an alarm 
condition. For LED keypads, the LED does not 
illuminate upon an alarm condition. Point text 
appears and annunciation is made for Invisible points 
programmed for a trouble condition in point response. 
 
To prevent the keypad alarm tone and the 
A# Burg Alarm bell from sounding, 
program P## Silent Bell as Yes
 
 
If a user enters a valid passcode while a 
bell is ringing for an invisible alarm, the 
keypad shows ALARM SILENCED.