Whirlpool WED6600WL Leaflet

Page of 1
®
Electric Dryer
PRODUCT MODEL NUMBERS
OVERALL DIMENSIONS
RECESSED AREA AND CLOSET INSTALLATION
EXHAUST VENTING
Because Whirlpool Corporation policy includes a continuous commitment to improve
our products, we reserve the right to change materials and specifications without notice.
Dimensions are for planning purposes only. For complete details, see Installation
Instructions packed with product. Specifications subject to change without notice.
Ref. W10164159B
07/2009
For closet installation
with a door, minimum
ventilation openings in
the top and bottom of
the door are required.
Louvered doors with
equivalent air openings
are acceptable.
1. Select the route that will provide the straightest and most direct path outdoors. Plan
the installation to use the fewest number of elbows and turns. When using elbows or
making turns, allow as much room as possible. Bend vent gradually to avoid kinking.
Avoid 90° turns.
2. Determine vent length.
The maximum length of the exhaust system depends upon:
• The type of vent (rigid metal or flexible metal).
• The number of elbows used.
• Type of hood.
See the exhaust vent length chart that matches your hood type for the maximum vent
lengths you can use.
3. Determine the number of elbows you will need.
IMPORTANT: Do not use vent runs longer than specified in the Vent Length Chart.
Electrical: A four-wire or three-wire, single
phase, 120-volt, 60 Hz, AC-only, electrical supply
is required on a separate 15 or 20 amp circuit,
fused on both sides of the line. A time-delay fuse
or circuit breaker is recommended.
Exhaust venting: Exhaust your dryer to the
outside. 4" (102 mm) diameter vent is required.
Rigid or flexible metal exhaust vent must be used.
Do Not use plastic or metal foil vent. Exhaust outlet
hood must be at least 12" (305 mm) from the
ground or any object that may be in the path of the
exhaust.
WED6600W
4"
(102 mm)
Louvered style
Angled style
4"
(102 mm)
4"
(102 mm)
Box hood style
2
1
/
2
"
(64 mm)
A. Recessed area
B. Side view - closet or confined area
C. Closet door with vents
 
Number of
90 turns 
or elbows
Type of
vent
Box or
Louvered 
hoods
Angled
hoods
0
Rigid metal
64 ft (20 m)
58 ft (17.7 m)
1
54 ft (16.5 m)
48 ft (14.6 m)
2
44 ft (13.4 m)
38 ft (11.6 m)
3
35 ft (10.7 m)
29 ft (8.8 m)
4
27 ft (8.2 m)
21 ft (6.4 m)
Rigid metal
Rigid metal
Rigid metal
Rigid metal
o
29"
(737 mm)
22
1
/
4
"
(565 mm)
29
1
/
4
"
(743 mm)
43
1
/
2
"
(1105 mm)
14" max.*
(356 mm)
A
B
C
29"
(737 mm)
5"
(127 mm)
1"
(25 mm)
1"
(25 mm)
18"*
(457 mm)
3"*
(76 mm)
3"*
(76 mm)
29
1
/
4
"
(743 mm)
48"
2
*
(310 cm
2
)
24"
2
*
(155 cm
2
)