Precautions for Using a
Rack-mounted SP2060
Rack-mounted SP2060
If several SP2060 units (or a SP2060 unit together with oth-
er devices) are installed in a poorly-ventilated rack, the heat
generated by each unit may raise the temperature inside the
rack, preventing the SP2060 from performing as designed.
When mounting SP2060 units in a rack, please leave one
rack space vacant for every two units. You can attach a ven-
tilation panel to this space or leave it open to prevent exces-
sive heat build-up.
If the temperature inside the rack is expected to rise above 40
degrees Celsius or 104 degrees Fahrenheit (or if the ambient
temperature outside the rack is expected to rise above 30 de-
grees Celsius or 86 Fahrenheit), install a fan kit in the top
row of the rack. The fan must provide airflow of 1.6m
er devices) are installed in a poorly-ventilated rack, the heat
generated by each unit may raise the temperature inside the
rack, preventing the SP2060 from performing as designed.
When mounting SP2060 units in a rack, please leave one
rack space vacant for every two units. You can attach a ven-
tilation panel to this space or leave it open to prevent exces-
sive heat build-up.
If the temperature inside the rack is expected to rise above 40
degrees Celsius or 104 degrees Fahrenheit (or if the ambient
temperature outside the rack is expected to rise above 30 de-
grees Celsius or 86 Fahrenheit), install a fan kit in the top
row of the rack. The fan must provide airflow of 1.6m
3
/min
or more and static pressure of 5mmH
2
O or more.
Fan kit
SP2060
SP2060
SP2060
SP2060
Ventilation panel