10 - ELECTRICAL WIRING
10.6 Thermostat
1. 
Connect room thermostat or end switch (isolated 
contact only) between terminals T1 and T2.
2. 
Install thermostat on inside wall away from influences 
of drafts, hot or cold water pipes, lighting fixtures, 
televisions, sun rays, or fireplaces.
3. 
Thermostat anticipator (if applicable)
A.  Set for 0.1 amps if connected directly to boiler.
B.  Set to match total electrical power requirements of 
connected devices if connected to relays or other 
devices. See device manufacturers’ specifications 
and thermostat instructions for details.
10.7 Outdoor Temperature Sensor
1. 
Connect outdoor temperature sensor between terminals 
A1 and A2 to enable outdoor reset operation of the 
boiler. If fixed temperature operation is required, do 
not install outdoor sensor.
2. 
Mount sensor on exterior wall, shielded from direct  
sunlight or flow of heat or cooling from other sources.
3. 
If desired, install a summer/winter switch across 
terminals A1 and A2. When the switch is closed, the 
boiler (space heating) circulator is disabled.
4. 
Route sensor wires through the holes provided on the 
right jacket panel of the boiler.
10.8 DHW Limit Control
Connect storage indirect water heater (DHW) limit control 
between terminals DHW T1 and DHW T2.
See Piping and Wiring Appendix for wiring and piping 
diagrams.
AVOID THE FOLLOWING
Dead Spots 
Corners
Alcoves
Behind doors
Cold Spots
Concealed pipes or ducts
Stairwells - drafts
Unheated rooms on the other side 
of the wall
Hot Spots
Concealed pipes
Fireplaces
TVs or radios
Lamps
Direct sunlight
Kitchens