Utica Boilers CuB Series Specification Sheet
ECR International, Inc.
2201 Dwyer Avenue, Utica NY 13501
Tel: 1-315-797-1310
Suggested Specifications Utica Boilers Copper Heating Boiler - 100/130
1.0
General Requirements:
1.1 Provide and Install Boiler(s) in accordance with the plan drawings, written specifications and
contract documents.
1.2 All work shall be performed in a neat workmanship like manner compliant with all local code
authorities.
2.0
Submittal
2.1 Product Data: Submit manufacturer’s technical product data, including rated capacities
of selected model, weights (shipping, and nstalled), installation and start-up instructions, and
furnished accessory information.
2.2 Shop Drawings: Submit manufacturer’s end assembly drawings indicating dimensions, connection
locations, and clearance requirements.
2.3 Wiring Diagrams: Submit manufacturer’s electrical requirements for the boiler including ladder
type wiring diagrams for interlock and control wiring.
3.0
Boiler Requirements
3.1 Boiler shall provide hot water for heating zones and shall include separate dedicated connections
3.1 Boiler shall provide hot water for heating zones and shall include separate dedicated connections
to provide hot water to an indirect tank.
3.2 Boiler shall accept a wired sensor to control an indirect tank and provide temperature reporting of
the indirect tank.
3.3 Boiler shall be certified for Category I and Category III operation.
3.4 Boiler shall be a wall hung model. An optional floor mounting stand shall be available from the
3.4 Boiler shall be a wall hung model. An optional floor mounting stand shall be available from the
manufacturer. Boiler shall be factory fire tested.
4.0
Acceptable Manufacturers
4.1 Equivalent units and manufacturers must meet all performance criteria for all fuel options, and will
4.1 Equivalent units and manufacturers must meet all performance criteria for all fuel options, and will
be considered upon prior approval.
5.0
Certifications & Listings
5.1 Boiler shall be certified by CSA, AHRI
5.2 Boiler shall be constructed in accordance with the American Society of Mechanical Engineers
5.1 Boiler shall be certified by CSA, AHRI
5.2 Boiler shall be constructed in accordance with the American Society of Mechanical Engineers
(ASME)
5.3 Boiler shall have an ASME H stamp that is applied to the heat exchanger. Each heat exchanger
shall be independently reviewed by an ASME authorized inspector. The boiler shall be rated for a
maximum allowable working pressure of 43.5 psig. The boiler shall be equipped with a 30 psig
relief valve.
6.0
Construction
6.1 Boiler heat exchanger shall be constructed of copper tube with copper fins, stainless steel support
6.1 Boiler heat exchanger shall be constructed of copper tube with copper fins, stainless steel support
plates and be covered with a high temperature protective coating.
6.2 Burner Components
6.2.1 Gas valve shall be a modulating valve capable of firing from 100% input firing rate to 33%
input firing rate.
P/N 240010783 REV C, [02/2015]