Power-limited Wiring Requirements
2. Installation
PDRP-1001 Instruction Manual  PN 50734:D0  04/06/01
17
Observe polarity when connecting the batteries. Connect the battery cable (p/n 75203 or 75202, depending 
on terminal size of battery) to terminal J9 on the main circuit board using the plug-in connector provided. 
Connect red wire to positive (+) terminal and black wire to negative (–) terminal on opposing batteries. 
Do NOT connect battery interconnect wire at this time.  
Figure 5  Battery Installation and Connection
Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-
limited circuit wiring must remain at least 0.25 in (6.35 mm) away from any nonpower-limited circuit 
wiring. Furthermore, all power-limited circuit wiring and nonpower-limited circuit wiring must pass 
through separate knockouts and/or conduits.   
Figure 6  Power-limited Wiring Requirements
J3
J9
J2
AMP
TB5
MS
44
-B
A
Tc
onn
.c
dr
GEN
ALM2
TONE
SILENCE
ALARM
SILENCE
ALARM
ACTIVATE
SYSTEM
RESET
AC POWER
SYSTEM
ALARM
ALARM T EST
SUPERVISORY
SYSTEM
TROUBLE
CIRCUIT
TROUBLE
ALARM
SILENCED
POWER
TROUBLE
ZONE 1
ZONE 2
ZONE 3
ZONE 4
SW1
TB1
TB2 TB3
TB4
JP1
SUPV 1
SUPR 2
GEN
ALM1
J4
J5
J7
J8
OPT1
OPT2
J10
J3
J9
J2
AMP
J1
TB5
OUT#1
B+  A+   A–   B–
OUT#3
B+  B–
OUT#4
B+  B–
ALARM
NO  NC  C
OUT#2
B+  A+   A–   B–
IN #1
B+  A+   A–   B–
IN #2
B+  A+   A–   B–
IN #3
B+  A+   A–   B–
IN #4
B+  A+   A–   B–
TB1
LATCH
DISABLE
J2
TB1
TBL
J1
J2
7
   
   
    
 5
   
  
1
PO
W
ER
 L
IM
IT
ED
  
AC Power
MRP
44
-p
lwiri
ng
.cdr
Power-limited 
Circuits
Nonpower-limited 
Circuits
Power-limited Circuits
Nonpower-limited 
Circuits
Power-limited
Circuits