Output Circuits
Notification Appliance Circuits
The control panel provides two Style Z (Class A) or Style Y (Class B) Notification Appliance Circuits,
which are supervised and power-limited.
which are supervised and power-limited.
Each circuit is capable of 1.5 amps of current. Total current drawn from both NACs and both Releasing
Circuits (see "Releasing Circuits" on page 21) cannot exceed 2.25 amps.
Circuits (see "Releasing Circuits" on page 21) cannot exceed 2.25 amps.
Note: Refer to the "Appendix B: Compatible Devices" on page 39 for suitable devices.
• For DIP switch configuration, see "Setting Mode of Operation" on page 28.
• For non-silenceable service on NAC#1, see "Non-Silenceable Service" on page 34.
• Unused circuits must be connected with a dummy load as shown.
• For non-silenceable service on NAC#1, see "Non-Silenceable Service" on page 34.
• Unused circuits must be connected with a dummy load as shown.
Figure 9 Notification Appliance Circuits
TB2
M
R
P4
4-na
c.cd
r
Polarized
Horn
Horn
Polarized
Strobe
Strobe
Polarized
Bell
Bell
Style Z
(Class A)
4.7K, 1/2-Watt ELR
PN 71252 (UL listed)
PN 71252 (UL listed)
Unused Style Y Circuit
4.7K, 1/4-Watt ELR
PN 71252 (UL listed)
Style Y
(Class B)