Appendix C: NFPA Standard-Specific Requirements
Local Energy Municipal Box
48
PDRP-1001 Instruction Manual  PN 50734:D0  04/06/01
Local Energy Municipal Box
Using the 4XTM Transmitter Module for connection to a Local Energy Municipal Box.
• The Municipal Box circuit supervises for ground faults and opens (i.e. missing wire) but not for 
direct short between two wires. It is not a power-limited circuit.
• This application is not suitable for separate transmission of sprinkler supervisory or trouble 
conditions.
• Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms.  
Figure 26  Municipal Box Connection