Symmetricom 1000 User Manual

Page of 224
097-58001-02 Revision G – April 2008
TimeProvider User’s Guide 129
Chapter 4 Provisioning the TimeProvider
Provisioning Alarms
<aid> = INP1 or INP2
INPDISQ
Specified input has 
been disqualified or 
qualified as a possible 
system reference.
MN | MJ | 
CR
FLT 
DELAY
Yes
MN
MN
INPAIS
The specified input is 
receiving an Alarm 
Indication Signal.
1
MN | MJ | 
CR
IMMED
No
MN
MN
INPLOS
The specified input has 
Loss of Signal.
1
MN | MJ | 
CR
IMMED
No
MN
MN
INPOOF
The specified input is 
receiving an Out of 
Frame signal.
1
MN | MJ | 
CR
IMMED
No
MN
MN
INPFRQ
Specified input port’s 
calculated received 
frequency exceeds the 
pull-in range of the 
LO.This alarm condition 
disqualifies the input as 
a possible reference.
2
NR | NA | 
MN | MJ | 
CR
IMMED
No
MN
NR
INPPHASE
Specified input port’s 
phase measurement 
exceeds usable value.
NR | NA | 
MN | MJ | 
CR
IMMED
No
MN
MN
INPQL
The received SSM is of 
lesser quality than the 
provisioned QLEVEL for 
a specified input. This 
alarm occurs when you 
provision the input’s 
QLEVEL below the 
quality level of the LO.
NR | NA | 
MN | MJ | 
CR
IMMED
No
MN
MN
EXDSC
Input has had excessive 
discontinuities, indicated 
by more than 3 signal 
faults (OOF, BPV, CRC, 
or AIS) within a 5-minute 
window. The alarm 
clears when the 5- 
minute window contains 
less than 3 signal faults.
NR | NA | 
MN | MJ | 
CR
IMMED
No
MN
MN
Table 4-3.  Alarm Conditions and Defaults (Continued)
Alarm ID
Description of Alarm 
Condition
Possible 
Alarm 
Levels
Error 
Delay 
Default
Error 
Delay 
Editable?
Default Level
SSU 
Mode
SUB 
Mode