Rack-mountable Tray
3-46
Sixth Edition
95741
 
Install Host Interface Cables
The 9840 Tape Drive supports Fibre Channel and SCSI interfaces. This section 
contains:
Fibre Channel Cables (Rack-mount Tray)
Use the instructions below to install Fibre Channel cables for a drive or CSL:
CAUTION:
Cable damage. Fiber optic cables are easily damaged. Follow the 
guidelines in 
 to prevent damage to the 
cables. 
1. Mark each Fibre Channel cable with the device address and port.
2. Route the cable(s) from near the host, hub, or switch to the rack.
Note: Do not attach either end of the cable(s) at this time.
3. Route the Fibre Channel cable(s) for the first drive tray through the floor tile cutout then 
through the cable cutout in the floor of the rack, and up to the rear of the CSL or drive 
tray. 
4. Leave enough slack in the cable(s) to bend and connect to the drive port(s). 
5. Remove the rubber port plug from the selected drive port and clean the port.
Note: If you are unfamiliar with the cleaning procedure, see 
.
6. Remove the cable connector covers and clean the cable ends with wipes.
Note: If you are unfamiliar with the cleaning procedure, see 
.