Siemens Wireless Office Headset SIMATICS PCS7 User Manual

Page of 32
SIMATIC PCS 7 TeleControl system architecture
8
1)
Data buffering is limited to two SIMATIC S7 data blocks. Depending on the 
SIMATIC CPU, this corresponds to approx. 800 to 3 200 buffered frames. 
Spectrum of outstations and integration versions
Telecontrol protocol
SINAUT ST 7
Modbus
DNP3
IEC 870-5-
101
IEC 870-5-
104
Type of communica-
tion
Serial
Ethernet 
TCP/IP
Serial
Ethernet 
TCP/IP
Serial
Ethernet 
TCP/IP
Serial
Ethernet 
TCP/IP
Interface on the 
PCS 7 TeleControl OS
TIM 4R-IE
TCP/IP WAN 
router or/and 
TIM 4R-IE 
TCP/IP 
converter
 –
serial
TCP/IP 
WAN router
TCP/IP 
converter
 –
serial
TCP/IP 
WAN router
TCP/IP 
converter
 –
serial
TCP/IP 
WAN router
RT
U
/i
n
te
rf
a
ce
ET 200S with inte-
gral CPU (corre-
sponds to S7-314)
IM 151-7 CPU 
or 
IM 151-8 
PN/DP CPU
as well as
1 SI module 
Modbus
IM 151-8 
PN/DP CPU 
+ S7-
OpenModbus 
software / 
TCP PN-CPU
IM 151-7 CPU 
or 
IM 151-8 
PN/DP CPU
as well as
1 SI module + 
SIPLUS RIC 
library 
IM 151-8 
PN/DP CPU + 
SIPLUS RIC 
library
S7-300/
S7-300F
TIM 3V-IE
TIM 3V-IE
CP 341
CP 343 + 
SW library
TIM 3V-IE 
DNP3
TIM 3V-IE 
DNP3
CP 341 + 
SIPLUS RIC 
library
CP 343 + 
IEC on S7 
or integral 
PN interface 
+ SIPLUS RIC 
library
S7-400/
S7-400F
TIM 4R-IE
TIM 4R-IE
CP 441
CP 443 + 
SW library
TIM 4R-IE 
DNP3
TIM 4R-IE 
DNP3
CP 441 + 
SIPLUS RIC 
library
CP 443 + 
SIPLUS RIC 
library
or integral 
PN interface 
+ SIPLUS RIC 
library
S7-400H/
S7-400FH
TIM 4R-IE 
DNP3
TIM 4R-IE 
DNP3
ET 200M + 
2 x CP 341 + 
SIPLUS RIC 
library
CP 443 + 
SIPLUS RIC 
library 
Third-party station
Depends on type of station
Depends on type of station
Depends on type of station
Dialup lines
Dedicated line and 
radio networks
Master-slave
Peer-to-peer
Mesh networks
Time tagging in RTU
RTU time synchroniza-
tion
Data buffering in RTU
1)
1)
Routing with 
SIMATIC PDM
International standard
(many ver-
sions)
(many ver-
sions)
© Siemens AG 2011