 Module  
 
     H01 
Issued: 02/2008 
  Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET 
Preface         Notes         Startup with PROFIBUS         Startup with PROFINET         Program Example 
 
Note: 
A complete parameter list with a detailed description of all parameters, as well as overview diagrams 
of the internal program structure (function charts) are provided in the List Manual. 
 
The parameter description looks like this in the List Manual (principle): 
 
Read Mode Parameters 
 
BICO (if exist) 
È
 
 
 
r0063 
CO: Frequency actual value/Frequency actual val. 
 
CU240S 
CU240S DP 
   Ç 
CU/PM Variants 
Access level
: 3                     
Unit
: [Hz] 
 
 P-Group
: Control 
Data Type
: Floating Point 
Data Set
: - 
 
 
 
Write Mode Parameters 
        Index 
           È 
BICO (if exist) 
È
 
 
 
p0700[0...2] 
Selection of command source/Sel.Comm.Source 
 
CU240E 
CU240S 
   Ç 
CU/PM Variants 
Access level: 1
 
Quick startup
: YES 
Can be changed
: C, T 
Min
 
  P-Group
Commands 
  Active: NO 
 
  Max 
  6 
Data Type
: Unsigned 16 
Data Set
: CDS 
 
Factory setting
 
 
Here, the following is described: 
• Parameter number (possibly with index) 
• Parameter text  
• Access level (depends on P0003) 
• Parameter(P) group (depends on P0004) 
• Data type (Unsigned8, Unsigned16, Unsigned32, Integer 16, or floating point) 
• Quick commissioning Yes/No 
• Active Yes (modifying the parameter values is immediately effective after input), or No (the button 
"P" on the Operator Panel (OP) has to be pressed for the changes to become effective) 
• Data set: parameters that are associated with data sets are here assigned correspondingly with 
CDS (command data set) or DDS (drive data set). 
• Can be changed in the converter mode Startup C, Mode U, or Ready T 
• Unit if there is a physical measuring unit for this parameter 
• Min indicates the lowest value to which the parameter can be set 
• Max indicates the highest value to which a parameter can be set 
• Factory setting indicates the default value for the factory setting 
 
 
Note: 
Further details are provided in the List Manual.