  Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET 
Preface         Notes         Startup with PROFIBUS         Startup with PROFINET         Program Example 
 
3.5.3.2 
Manual Parameter Download from a MMC to the Converter 
 
Preconditions 
● The supply voltage has to be applied at the download converter 
● The download converter is in the "Ready Mode" 
● The directory structure /USER/SINAMICS/DATA/clonexx.bin 
has to be on the MMC 
 
Notes on the Download 
When performing the download, the following important conditions have to be met: 
• During the download, the converter does not respond to any commands. 
• Once the download is started, it can not be interrupted. 
• After uploading and downloading parameters between the different control units, the parameter 
settings have to be checked. 
• Downloading parameters from another CPU could possibly fail with F0063 if there are parameters 
that can not be loaded. 
• If the download fails, the previous EEPROM parameters are restored again on the converter. 
 