Emergency power supply 
55 
Siemens Building Technologies
 
 007836_a_en_--.doc
Fire & Security Products 
 
03.2004
 
 
23.3  Quiescent current table 
 
– 
Quiescent current when on battery operation (24V) 
– 
As basis for individual calculation of emergency power supply 
– 
The current for the 5V supply is included in these values 
 
Module 
Quiescent current at 24VDC
 
(typical) 
Additional current with alarm condition 
B2F020 0 
B3Q700 
100mA  LCD backlight ’inactive’ (active =  + 200mA) 
+ 230mA 
B3Q580 20mA 
160mA 
B3Q590/595 18mA 
167mA 
B3R051 
40mA 
all LEDs inactive 
+ 2mA 
per activated LED 
E3C011 20mA 
E3G050 
10mA 
all relays inactive 
+ 11mA  per activated relay 
E3G060 
25mA 
all control lines terminated 
+ 23mA  per activated control line, without external load 
E3G070 
25mA 
control line ’Horn’ terminated 
+ 34mA  without external load (horns etc.) 
E3H020 100mA 
E3I020 25mA 
E3L020 
22mA 
+   ..mA  depends from the activated device 
E3L030 
18mA 
+ 40mA  without external load (FBF, HM, FSK) 
E3M080 
85mA 
37mA + 6mA per terminated line 
+ 10mA  per line in alarm 
E3M111 
210mA  (=50mA + 0,31mA per D–Bus device)     1) 
 
(without external 24V load) 
K3G060 
6mA 
+ 3mA 
per relay 
K3R072 
40mA 
+ 2mA 
per activated LED 
per activated relay 
Z3B171 
+ 27mA  per activated relay 
E3I040 
15mA 
without external 24V load 
K3I050 
15mA 
+ 0mA 
or 4mA per activated LED 
K3I110 
24mA 
max. 184mA all relay activated incl. service LED 
+ 10mA  per activated relay 
+ 0,5mA  per input with closed contact 
Only valid for device with APMK = 1  (multiply value for devices > 1)