Commissioning (software) 
 
4.6 Using drive-related I/Os by SIMOTION 
 
D410 
86
 
Commissioning Manual, 08/2008 Edition 
Configuration 
Description 
Applications 
Supported I/Os 
(drive objects) 
Expanding a message 
frame 
For the data transmission of the I/O 
data, existing message frames are 
extended with the process status 
data (PSD). These additional PSDs 
must then be interconnected using 
BICO. 
Preferred solution when I/Os are 
to be divided between 
SIMOTION and SINAMICS and, 
for example, an axis view is 
preferred. (Drive-related I/Os are 
appended to each axis message 
frame.) 
• 
Onboard I/Os on 
the D410 
• 
Onboard I/Os on 
CU310 
• 
TM15 DI/DO 
• 
TM31 
• 
TM41 
 
 
 
Note 
The module hardware for TM15 and TM15 DI/DO is identical. The differentiation is made 
only with the addition of the component in the Project Navigator of the SIMOTION SCOUT 
using "Inserting input/output component". 
Further information about the TM15 and TM17 High Feature is contained in the 
TM15 and 
TM17 High Feature
 Commissioning Manual. 
 
 
Note 
The "free message frame configuration using BICO" and the "message frame extension" 
allow you to use inputs/outputs channel-granular by SIMOTION or SINAMICS. 
For message frame 39x, however, all onboard terminals are interconnected automatically to 
message frame 39x using BICO interconnections and so available only for SIMOTION. The 
following is true: 
• 
All onboard I/Os configured as digital output for the drive are only available for 
SIMOTION, i.e. they can no longer be used by SINAMICS. 
• 
Digital inputs can be used by SIMOTION and SINAMICS.