Program Mode Entry 
Upon initial power application, the SITRANS LU01 displays OFF.
To enter PROGRAM mode
1.
Secure the enclosure lid using the 6 captivated screws. 
2.
Place the infrared programmer in the enclosure lid recess.
3.
Press PROGRAM 
 
and then press DISPLAY 
.
When PROGRAM mode is entered after RUN mode operation, all operating data is 
retained in memory. Relay status and mA output values are held at last known values 
(unless affected by a parameter alteration or 
 
transducer firing) until RUN mode is re-
entered. RUN mode is automatically re-entered if the SITRANS LU01 is left unattended in 
PROGRAM mode for an extended period. 
Changing Parameters
Enter the new value, and press ENTER 
. The SITRANS LU01 interprets the value, 
either accepting or replacing it with a valid value. 
1.
Starting in RUN mode, press PROGRAM 
 
and then press DISPLAY 
 to put the 
unit into PROGRAM mode.
2.
Press DISPLAY 
 to select the Parameter Number field.
3.
Key in the desired Parameter Number, or press SCROLL 
 
or 
 
as required . 
After the third digit is entered, the parameter value is shown.
(By default, the SCROLL arrows 
 
 
show only the Quick Start Parameters and any 
that have been changed).
4.
Press DISPLAY 
 
as required to underline the Index display field. 
5.
Key in the desired Index or press SCROLL 
 
or 
 
as required.
To alter the Parameter Value for all Indices at once, select Index 00. 
Enter the new value, and press ENTER 
. The SITRANS LU01 interprets the value, 
either accepting or replacing it with a valid value. .
Notes:
Record each Parameter Value alteration on the appropriate Programming 
Chart for future reference, (especially should complete reprogramming be 
required). 
If Parameter Value alteration is not permitted, access the Lock parameter 
(P000) and enter the security code (See Programming Security).