SITRANS LU01 – INSTRUCTION MANUAL
7ML19985BE02
Pa
ra
m
e
te
rs
Independent mA Setpoints (P210 and P211) 
Use these features to reference the minimum and/or maximum mA output to any point in 
the measurement range. 
P210 0/4 mA Output Setpoint
Sets the process level corresponding to the 0 or 4mA value.
Enter the value (in applicable units or %) to correspond to 0 or 4 mA.
P211 20 mA Output Setpoint
Sets the process level that corresponds to the 20 mA value.
Enter the value (in applicable units or %) to correspond to 20 mA.
mA Output Limits (P212 and P213)
Use these features to adjust the minimum and/or maximum mA output values, which 
should suit the input limit requirements of the external device.
P212 mA Output Min Limit
Sets the minimum mA output value (in mA) to be produced.
P201—mA 
Function Settings
Action
Level, Space, or Distance
Enter the material level in Units (P005) or percent of Span 
(P007) as referenced to Empty (P006).
Volume 
Enter the volume in Max Volume (P051) units or as a per-
cent of Max Volume.
Volume Rate 
Enter the volume rate in volume/min. Ensure the % symbol 
is displayed before attempting to enter a % value.
mA input or
Communications Input
Not Applicable
Primary Index
mA output
Values
Range: -999 to 9999
Related
P211 20 mA Output Setpoint
Primary Index
mA output
Values
Range: -999 to 9999
Related
P210 0/4 mA Output Setpoint
Primary Index
mA output
Values
Range: 0.000 to 22.00
Preset: 0.0 or 3.8
Related
P200 mA Output Range
P213 mA Output Max Limit