Sea Frost DC 5000 User Manual

Page of 46
 
3
There are three conditions of charge indicated by the sight glass: 
 
1. A black or clear glass and no cooling indicates no charge.  Turn off the 
compressor at once. 
2.  A white foaming glass and some cooling indicates the system is undercharged or 
has lost charge.  Refer to the manual regarding leak checking and adding 
charge. 
3.  A black glass and proper cooling indicates all is well. 
 
  
RFD SIGHT GLASS DETAIL 
 
EMPTY OR CLEAR 
STATIONARY BUBBLES 
FOAM/LOW 
 
 
Feel the SEA FROST Plate in the icebox ten minutes after engaging the timer switch.  If 
the sight glass clears yet the plate temperature does not drop after 10 minutes of 
operation, turn off the system and CALL US AT 603-868-5720.   
 
 
Inspecting the sight glass periodically for several weeks after a new installation and 
every time after a lay period is assurance that your SEA FROST DC 5000 system is 
assembled properly and is a good maintenance habit as well.