Testing (Cont) 
                                                                         
 
IF UNIT FAILS TO OPERATE PROPERLY 
ISSUE CHECK 
Unit will not operate 
— 
Verify
 that Red "Power" light is illuminated. 
—  Verify that line voltage is present between terminals 1 and 3 of indoor unit. 
—  Turn unit on with remote. (you should hear a "Beep" from indoor unit). Allow 
3-4 min. for unit to restart. 
—  Turn unit to "Test" mode. Verify that cooling function works (allow 3-4 min. 
for unit to restart.) 
Compressor will not operate 
—  Turn unit to Cool mode. Allow 3-4 min for compressor timer to operate. 
Check for line voltage between pins 1 and 2 of indoor unit. If no voltage is 
present please call technical support. 
The unit vibrates during operation 
—  Is the indoor unit firmly attached to the wall? 
—  Is the front cover closed properly? 
Inefficient Cooling (heating) 
—  Was the refrigerant leakage test performed with good results? 
—  Are the air flow grills (inlet and outlet free from obstructions?) 
—  Was refrigerant added as necessary? 
Appearance of water or condensation. 
—  Were refrigerant lines completely covered with insulation? 
—  Is condensate drain routed properly (downward)?