Step 3: Wire the Voltage and Current Inputs
Voltage Inputs
Current Inputs: High Current Option
Current Inputs: Low Current Option
N
OTE
The appropriate Volts Mode setting is included with each wiring diagram.
Refer to Step 7 to learn how to configure Volts Mode on the meter.
CT & PT Selection
Consult your local instrument transformer expert, either at the local utility or 
through a vendor or supplier, to obtain CT and PT selection standards for 
high accuracy revenue metering applications in your regions.
Inputs
U1, U2, U3, Uref
Accuracy and Rating 
Range
57 - 288 L-N VAC RMS 
99 - 500 L-L VAC RMS
Fault Capture
1200 V peak (L-N)
Overload
1500 VAC RMS continuous
Dielectric Withstand
3320 VAC RMS at 50 Hz for 60 s
Input Impedance
5 MΩ/phase (phase - Vref)
Rating
Measurement category IV
Accuracy Range
0.05 - 10 A autoranging
Rated Nominal
5 A
Starting Current
0.001 A RMS
Max. Current
10 A
Fault Capture
14 A peak
Max. Voltage
288 V RMS (Cat IV IEC 61010-1)
Overload
200 A RMS for 0.5 s, non-recurring
Dielectric Withstand
3320 VAC RMS at 50 Hz for 60 s
Burden
0.25 VA per phase (at 5 A)
Impedance
10 mΩ per phase
Rating
Measurement category IV
Accuracy Range
0.01 - 6 A autoranging
Rated Nominal
1 A and 2 A
Starting Current
0.001 A RMS
Max Current
10 A
Fault Capture
14 A peak
Max. Voltage
288 V RMS (Cat IV IEC 61010-1)
Overload
200 A RMS for 0.5 s, non-recurring
Dielectric Withstand
3320 VAC RMS at 50 Hz for 60 s
Burden
0.01 VA per phase (at 1 A)
Impedance
10 mΩ per phase
Rating
Measurement category IV