Step 5: Wire the Power Supply
ION8800 meter power supply connections are found on the Essailec 
connector.
Single Phase Power Supply
Step 6: Power Up the Meter
D
ANGER
Before  you  apply  power  to  the  meter,  ensure  that  ground  is  securely
connected and that the supply voltage is within the allowed range of the
meter’s power supply.
Step 7: Set Up the Meter Using the Front Panel
The following Setup screens are available for meter configuration via the 
front panel:
The following example shows Volts Mode setup using the meter front panel.
Fuse for N/- 
terminal required if 
neutral is 
ungrounded.
Rated Inputs 
85 - 240 VAC ±10%
 
(47 - 63 Hz)
110 - 270 VDC ±10%
Rating
Installation category II (local), Pollution degree 2
Dielectric Withstand 
2,000 VAC RMS for 60s (50Hz)
Max. Burden
9 W (20 VA) for base unit without comm module
Ride-through
Min: 120 ms (6 cycles @ 50 Hz)
Typical: 0.5 - 5 s (depending on input voltage and 
configuration)
BASIC SETUP
DEMAND SETUP
COM1 SETUP
COM2 SETUP
COM3 SETUP
COM4 SETUP
NETWORK SETUP
FORMAT SETUP
DISPLAY SETUP
SECURITY SETUP
Press 
ALT
/
ENTER
 and 
hold for 3 seconds 
to 
enter Setup Mode 
from Display Mode.
Use arrow buttons to 
move up and down in 
list. Press 
ALT
/
ENTER
 to 
select Basic Setup.
Use arrow buttons to 
move up and down in 
list. Press 
ALT
/
ENTER
 to 
select Volts Mode.
Use arrow buttons to 
move up and down in 
list. Press 
ALT
/
ENTER
 to 
select 
4
W
-
WYE
.
Press and hold
Press
Press
Press
Press