Schneider Electric Weather Radio ION8800 User Manual

Page of 36
26 
© 2007 Schneider Electric.  All rights reserved.
The following table lists all settings that can be configured using the ALT 
CONFIG menu (not available when meter cover is sealed). 
1
After a meter is unlocked, it automatically relocks if you do not perform any 
configuration for 30 minutes. This function is not available on non-
hardware lockable meters.
2
Default = ‘Locked’ on meters ordered with Hardware Lock option.
Default = ‘Unlocked’ on all other meters (setting is non-functioning).
Step 8: Verify Meter Operation
Three LEDs on the left-hand side of the Front Panel indicate the following:
Phasor Diagrams
You can also view the meter’s phasor diagram in real time. Use the Phasor 
Viewer available in ION Setup v2.1 and later (free to download from the 
website) to verify your meter’s wiring. See the ION Setup online help for 
details.
N
OTE
The following DELTA phasor diagrams are represented in system mode.
DELTA phasors for UNITY Power Factor (resistive load)
Applicable Volts Mode = DELTA
Setting
Description
Range (Values)
Default 
IR Config
Allows meter configuration via the front optical port
Disabled or Enabled
Enabled
Meter Lock
1
When meter is locked, most meter configuration is 
prevented, as are meter resets
Locked or Unlocked
Locked
2
Clear Alarms
Sends a pulse to clear alarms when pushed
-
-
Alarm (red) Top LED is user programmable; by default, it flashes to indicate 
serious meter faults. Contact Technical Support if this occurs.
Indicator (green) Middle LED is user programmable.
Power (green) Bottom LED indicates the meter is powered. The light should 
always remain on when the meter is in service.
I1 
I3 
I2 
U12
U23 
U31 
I1 
I3
I2
U12 
U23
U31
Rotation 123 
Rotation 132