18 
© 2007 Schneider Electric.  All rights reserved.
Step 6: Wire the Power Supply
Step 7: Power Up the Meter
1.
Ensure the ground wire is securely connected on both ends.
2.
Ensure the meter’s power supply voltage is within the allowed range. 
3.
Power up the meter.
Step 8: Set Up the Meter Using the Front Panel
The following Setup screens are available for meter configuration via the 
front panel:
Use the 
PROG
/
SELECT
ESC
, softkeys and arrow buttons to configure settings. 
The following example shows Volts Mode setup using the meter front panel.
Specification
Standard Power Supply
Low Voltage DC
Type 
Captured wire connector
Wire 
3.3-2.1 mm
2
 (12-14 AWG)
2.1-0.8 mm
2
 (14-18 AWG)
Rated Inputs 
85-240 VAC ±10%
 
(47-63 Hz), 
or 110-300 VDC ±10%
20-60 VDC ±10%
Dielectric Withstand  2500 VAC RMS at 60 Hz for 60s
Burden 
35 VA max. (15 VA typical)
18 W max. (12 W typical)
Ride-through 
100 ms (6 cycles at 60 Hz) min. None
G
N
_
L
+
BASIC SETUP
COM1 SETUP
COM2 SETUP
COM3 SETUP
COM4 SETUP
NETWORK SETUP
PQ SETUP
FORMAT SETUP
DISPLAY SETUP
TIME SETUP
SECURITY SETUP
METER RESETS
Press 
PROG
/
SELECT
 to 
enter Setup Mode 
from Display Mode.
Use arrow buttons to 
move up and down in 
list. Press 
PROG
/
SELECT
 
to select Basic Setup.
Use arrow buttons to 
move up and down in 
list. Press 
PROG
/
SELECT
 
to select PT/CT Setup.
Press Mode softkey. 
Use arrow buttons to 
move up and down in 
list. Press 
PROG
/
SELECT
 
to select Delta.
Press
Press
Press
Press
Press
Press