Chapter 5—Setup
9/2002
Configuring the Power Server
27
© 2002 Schneider Electric All Rights Reserved
Configuring Your POWERLOGIC System
While in setup mode, you can add devices to the 
POWERLOGIC
 System. 
Serial connections for COM 3 and COM 4 of the Power Server are already 
defined in the system. Do not delete these settings or define a new 
communication connection for COM 3 or COM 4 ports
.
To add devices to the Power Server, follow these steps.
1. Double click the PowerLogic Server icon 
 on the desktop to launch 
the application. 
2. For user ID, enter: master 
3. For password, enter: master, then click OK.
4. Double click the PowerLogic System Setup icon 
 on the desktop to 
launch the application. 
5. For user ID, enter: master 
6. For password, enter: master, then click OK once the 
POWERLOGIC
 
System Setup is started.
7. Select File > Offline to place the 
POWERLOGIC
 System offline.
8. Configure the system by defining the communication connections and 
adding devices. To do this, select Setup > Communications and then 
Setup > Devices/Routing.
NOTE: If you need help configuring the PowerLogic system, refer to the 
online help file “Quick Starts” listed in the help contents. From the 
PowerLogic System Setup utility, click Help > SMS-3000 Help > Quick 
Starts > Quick Start: Serial Device Setup.
9. Depending on the type of Power Server you have and functions required, 
perform setup procedures as needed for:
• Alarms
• Reports
• Waveforms
• Diagrams
Refer to the Power Server user’s guide 63230-216-217 for details.
10. After configuring the system, place the 
POWERLOGIC
 system back 
online by selecting File > Online > System.
The Power Server has only one system, which is always open for editing. 
It should always be left online except during configuration.
11. Close the 
POWERLOGIC
 System setup application.
12. Set the Power Server to run mode.
CAUTION
POSSIBLE LOSS OF COMMUNICATIONS
Ensure that your 
POWERLOGIC
 system is online before exiting 
POWERLOGIC System Setup.
Failure to do so will result in communication errors.