PowerMax DE5450 User Manual

Page of 16
10
DE5450
5.2 Replacing the Backup Battery
CAUTION! If you replace rechargeable cells
with alkaline (dry) cells, be sure to install the
battery-type jumper in the “DRY” position.
Failure to do so will result in rapid cell
destruction and leakage (acid leakage may
cause further damage).
Figure 31. Jumper in Dry Battery Position
Replacement and first-time insertion of cells are similar
(see Para. 3.2). The only difference is the necessity to
remove the old cells and to inspect the battery holder
contacts and springs for signs of corrosion.
If corrosion is found in the battery holder, clean it first with
a piece of cloth dampened with hot water and then file the
contacts clean until they shine. In extreme cases, the
entire battery holder should be replaced.
With fresh battery cells, correct insertion and tightened
battery compartment lid, the TROUBLE indicator should
extinguish. However, the “MEMORY” message will now
blink in the display (caused by the “tamper” alarm you
triggered when opening the battery compartment lid).
Clear it by arming the system and immediately disarming.
5.3 Fuse Replacement
The PowerMax has two fuses which can burn out:
 
 
Battery Fuse - 1A, time delay type, UL recognized
(exists in U.S. variants only).
 
 
Siren Fuse - 0.5 A, time delay type, UL recognized (in
the U.S.A.) or 0.5 A, time delay type, per IEC127-3 (in
Europe).
If any one of the fuses burns out (in U.S.A. variants) or the
siren fuse burns out (in other variants), the trouble
indicator lights and TRBL is displayed (together with
READY or NOT READY - as the case may be). Clicking
the <SHOW /OK> button will display a FUSE TROUBLE
message.
The fuse(s) is (are) accessible through the rectangular
opening at the rear of the cabinet (see figure 32). To
replace a fuse, the cabinet should be temporarily
dismounted (as described in Para. 5.1 above).
Extract the suspected fuse and check it visually. In most
cases, a defective fuse can be identified by the broken
conductor within the glass cylinder. If in doubt, test the
continuity of the fuse with an ohmmeter.
Replace a defective fuse with a new one of the same
ratings. The relevant trouble indications will immediately
disappear.
Figure 32. Fuse Locations
5.4 Replacing/Relocating Detectors
Whenever the maintenance work involves replacement or
re-location of detectors, you must keep in mind the
requirement to provide a 6 dB safety margin for signal
reception.  It is therefore mandatory to perform a full
diagnostic test per Section 9 of the Programming Guide.
Remember! 
A "poor" signal is not acceptable, as stated at
the end of the test procedure.