Parker Products COMPAX-M /-S (L) User Manual

Page of 242
Positioning and control functions
Engaging and disengaging the motor brake
123
Unit
hardware
Connector
assignment / cable
Technical data
Configuration
Positioning and
control functions
Optimization
functions
Interfaces
Accessories /
options
Status
Parameter
Error list
8.4.35  Engaging and disengaging the motor brake
COMPAX controls the idle holding brake of the motor and final stage. The time
behaviour can be set using P17 and P211 Bit 2.
If you are using an axis which is under torque when idle (e.g. when using a z axis),
the drive can be engaged and disengaged in a manner which ensures that the load
does not move. To do this, the drive remains powered during the reaction time of
the idle holding brake. This can be set using P17 (see following diagrams).
Final stage blocked by:
 
error or
 
OUTPUT O0="1" or
 
emergency STOP.
The final stage is enabled via:
 
quit or
 
OUTPUT O0="0" or
 
once Power is on
with P211 Bit 2="0".
The final stage is enabled
via:
 
OUTPUT O0="0"
P211 Bit 2="1"
(the lag of 0.5s is switched off)
P17=0
t
disabled
power out-
put stage 
enable
t
de-energised
t
close
brake
open
energised
t
t
t
0,5s
disabled
power out-
put stage 
enable
de-energised
close
brake
open
energised
t
t
t
disabled
power out-
put stage 
enable
de-energised
close
brake
open
energised
P17>0
t
t
t
P17
disabled
power out-
put stage 
enable
de-energised
close
brake
open
energised
t
disabled
power out-
put stage
enable
t
de-energised
energised
t
close
brake
open
0,5s
P17
t
t
t
P17
disabled
power out-
put stage 
enable
de-energised
close
brake
open
energised
Meaning
Unit
Min. Value
Standard
Maximum value
Applies to ...
Braking delay
ms
0
0
500
VP
Application:
Range of values
for P17: